The width and height should be the same as the cooling coil. The capacity of theheating coil should not exceed that of the cooling coil otherwise the cooling effectwill decrease. To accommodate the heating coil, additional cooling capacity isrequired. For example, if the customer requires 50kW of cooling capacity followed by10kW of heating, then the cooling capacity should be increased by 10kW. If not, thenett cooling capacity will be only 50kW-10kW=40kW.