Short-circuit characteristic :
- Rated conditional short-circuit current (kA)....................: N/A
- kind of protective device ...............................................: N/A
Releases :
1) shunt release ..............................................................: N/A
2) Over-current release ...................................................: Yes
a) instantaneous .............................................................: Yes
b) definite time delay ......................................................: N/A
c) inverse time delay .......................................................: Yes
- independent of previous load ........................................: N/A
- dependent on previous load; (for example thermal type
release)...........................................................................:
Thermal type
3) Undervoltage release (for opening) .............................: N/A
4) Other releases ............................................................: N/A
Characteristics :
1) Shunt release and undervoltage release (for opening)
- rated control circuit voltage: Uc ( nature, frequency, V) : N/A
- kind of current ...............................................................: N/A
- rated frequency: (if AC).................................................: N/A
2) Over-current release
- rated current .................................................................: EasyPact CVS100B/F: 16, 25, 32, 40, 50, 63,
80, 100 A
EasyPact CVS160B/F: 125, 160 A
EasyPact CVS250B/F: 200, 250 A
- kind of current ...............................................................: AC
- rated frequency: (if AC).................................................: 50 / 60 Hz
- current setting (or range of settings) ..............................: Inverse time delay: 0,7 ~ 1 In
Instantaneous tripping:
Ii (In): 190 A (16 A) / 300 A (25 A) / 400 A (32
A) / 500 A (40 A) / 500 A (50 A) / 500 A (63 A) /
640 A (80 A) / 800 A (100 A) / 1250 A (125 A) /
1250 A (160 A) / 2000 A (200 A) / 2500 A (250
A) for 2 phase poles in series,
1,2 Ii for single pole
- time settings (or range of settings) ................................: Inverse time delay: fixed
Instantaneous tripping: fixed
Page 8 of 80 Report No. 3302407.50
TRF No. IEC60947_2F
Classification of installation and use............................... : Fixed
Supply Connection ......................................................... : 3 phase or 3 phase with Neutral
Possible test case verdicts:
- test case does not apply to the test object .............. : N/A
- test object does meet the requirement ................... : P (Pass)
- test object does not meet the requirement ............. : F (Fail)
Testing
Date of receipt of test item ....................................... : 2011-6
Date (s) of performance of tests ............................... : 2011-7~11
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing
laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
EasyPact CVS series B type and Easypact CVS series F type are fully identical except the different shortcircuit
break capacity on the marking.
Therefore, EasyPact CVS series B type was subjected to full test program with the rating of F type to
cover both types.
EasyPact CVS series MCCB in this report and Vigi CVS series MCCB in report 3302407.51 are identical
except that Vigi CVS series MCCB is equipped with additional residual current unit. Therefore, the
following tests on Vigi CVS series MCCB are deemed to cover the tests of EasyPact CVS series MCCB:
- Seq I
- Seq II (except for In max with max short circuit current)
- Seq III (phase + N test)
- Annex H on construction breaks
This report shall be read in conjunction with report 3302407.51 as well.
Throughout this report a comma is used as the decimal separator.
Though it is not mentioned on the first page, the following standard was also taken into consideration. No
deviation was found:
EN 60947-2:2006 +A1:2009
General product information:
The products for testing are a series of moulded - case circuit breakers in one frame with 3 construction
breaks:
EasyPact CVS100B/F: 16, 25, 32, 40, 50, 63, 80, 100 A
EasyPact CVS160B/F: 125, 160 A
EasyPact CVS250B/F: 200, 250 A,
For other technical data, refer to page 5 to 7 of this report.
Factory location 1: Schneider (Beijing) Medium & Low Voltage Co., Ltd.
No.2 Liang Shui He 2nd Street, Beijing Economic Technological Development Area, Beijing, China
Factory location 2: Schneider Electric India Private Limited
Survey #215, Gagillapur Village, Medak Road, Hyderabad, Andhra Pradesh, India
Page 9 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
5.2 MARKING
a) The following data shall be marked on the circuit-breaker itself or on a name plate
or nameplates attached to the circuit-breaker, and located in a place such that they
are visible and legible when the circuit-breaker is installed.
- rated current: 250 A P
- suitability for isolation, if applicable, with the
symbol
P
- indication of the open and closed position:
with and I respectively, if symbols are
used
P
b) Marking on equipment not needed to be visible after mounting:
- manufacturer's name or trademark Schneider Electric P
- type designation or serial number EasyPact CVS250B P
- IEC 60947-2 if the manufacturer claims
compliance with this standard.
IEC/EN 60947-2 P
- utilization category A P
- rated operational voltage(s) Ue 220 / 240 V, 380 / 415 V,
440 V
P
- Circuit-breaker for use in IT systems:
Circuit-breaker for which all values of rated voltage
have not been tested according to annex H or are
not covered by such testing, shall be identified by
the symbol which shall be marked on the circuitbreaker
immediately following these values of
rated voltage
Suitable for IT systems P
- value (or range) of the rated frequency and/or
the indication DC (or symbol)
50 / 60 Hz P
- rated service short-circuit breaking capacity. Ics 40 kA at 220 / 240 V
25 kA at 380 / 415 V
15 kA at 440 V
P
- rated ultimate short-circuit breaking capacity. Icu 40 kA at 220 / 240 V
25 kA at 380 / 415 V
20 kA at 440 V
P
- rated short-time withstand current, (Icw) and
associated short-time delay, for utilization
category B
N/A
- line and load terminals, unless their connection is
immaterial
connection is immaterial N/A
Page 10 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
- neutral pole terminals, if applicable, by the letter
N
P
- protective earth terminal, where applicable, by the
symbol acc. 7.1.9.3 of part 1
N/A
- ref. temperature for non-compensated thermal
releases, if different from 30°C
40 oC P
c) Marked on the circuit-breaker as specified in item b), or shall be made available in
the manufacturer's published information:
- rated short-circuit making capacity (Icm)
(if higher than specified in 4.3.5.1)
N/A
- rated insulation voltage. (Ui) if higher than the
maximum rated operational voltage)
690 V P
- rated impulse withstand voltage (Uimp), when
declared.
8 kV P
- pollution degree if other than 3 N/A
- conventional enclosed thermal current (Ithe) if
different from the rated current:
N/A
- IP Code, where applicable: IP40 for front cover P
- minimum enclosure size and ventilation data (if
any) to which marked ratings apply:
N/A
- details of minimum distance between circuitbreaker
and earthed metal parts for circuit-breaker
intended for use without enclosure:
Up / down: 35 mm
Left / right: 5 mm
Front / back: 0 mm
P
- r.m.s sensing if applicable, according to F.4.1.1 N/A
- suitability for environment A or B A and B P
d) The following data concerning the opening and closing devices of the circuitbreaker
shall be placed either on their own nameplates or on the nameplate of the
circuit-breaker:
- rated control circuit voltage of the closing device,
and rated frequency for AC:
N/A
- rated control circuit voltage of the shunt release
and/or of the under-voltage release, and rated
frequency:
N/A
- rated current of indirect over-current releases: N/A
- number and type of auxiliary contacts and kind of
current, rated frequency (if AC) and rated voltages
of the auxiliary switches, if different from those of
the main circuit.
N/A
Page 11 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
e) Terminal shall be clearly and permanently identified in acc. with IEC 60445 and
annex L :
- line terminal N/A
- load terminal N/A
- neutral pole terminal ”N” P
- protective earth terminal N/A
- terminal of coils (A/B) N/A
- terminal of shunt release ( B ) N/A
- terminals of under-voltage release (D) N/A
- terminals of interlocking electromagnets (E) N/A
- terminals of indicated light devices (X) N/A
- terminals of contact elements for switching
devices (no)
N/A
Page 12 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
7.1 CONSTRUCTION P
7.1.1 Withdrawable circuit-breaker N/A
In the disconnected position (main- and auxiliary circuits)
Isolating distances for circuit-breaker suitable for
isolating warranted:
N/A
Mechanism fitted with a reliable indicating device
with indicates the position of the isolating contacts.
N/A
Mechanism fitted with interlocks which only permit
the isolating contacts to be separate or re-closed
when main contacts are open
N/A
Mechanism fitted with interlock, which only permit
the main contacts to be closed when the isolating
contacts are fully closed.
N/A
Mechanism fitted with interlock, which only permit
the main contacts to be closed when in
disconnected position.
N/A
The isolating distances between the isolating
contacts cannot be inadvertently reduced.
N/A
7.1.2.1
part 1
Resistance to abnormal heat