The stability of bus protection is of paramount importance. Bearing in mind the low rate of fault incidence, amounting to no more than an average of one fault per busbar in twenty years, it is clear that unless the stability of the protection is absolute, the degree of disturbance to which the power system is likely to be subjected may be increased by the installation of bus protection. The possibility of incorrect operation has, in the past, led to hesitation in applying bus protection and has also resulted in application of some very complex systems. Increased understanding of the response of differential systems to transient currents enables such systems to be applied with confidence in their fundamental stability. The theory of differential protection is given later in section 15.7.