It can be observed in Figure 11.11

It can be observed in Figure 11.11 how the load area is defined
according to a minimum impedance arc, constrained by
straight lines which emanate from the origin, 0. Modem
numerical relays typically do not use lenticular characteristic
shaping, but instead use load encroachment (load blinder)
detection. This allows a full mho characteristic to be used, but
with tripping prevented in the region of the impedance plane
known to be frequented by load (ZA-ZB-ZC-ZD).

The previous section showed how the non-directional offset
mho characteristic is inherently able to operate for close-up
zero voltage faults, where there would be no polarising voltage
to allow operation of a plain mho directional element. One
way of ensuring correct mho element response for zero-voltage
faults is to add a percentage of voltage from the healthy
phase(s) to the main polarising voltage as a substitute phase
reference. This technique is called cross-polarising, and it has
the advantage of preserving and indeed enhancing the
directional properties of the mho characteristic. By the use of
a phase voltage memory system, that provides several cycles of
pre-fault voltage reference during a fault, the cross-
polarisation technique is also effective for close-up three-phase
faults. For this type of fault, no healthy phase voltage
reference is available.
0/5000
Từ: -
Sang: -
Kết quả (Việt) 1: [Sao chép]
Sao chép!
Nó có thể được quan sát trong hình 11,11 cách khu vực tải xác địnhtheo một vòng cung tối thiểu trở kháng, hạn chế bởiđường thẳng xông lên từ nguồn gốc, 0. Modemsố rơ le thường không sử dụng lenticular đặc trưngtạo hình, nhưng thay vì sử dụng tải xâm lấn (tải blinder)phát hiện. Điều này cho phép một đặc tính đầy đủ mho được sử dụng, nhưngvới tripping ngăn chặn trong vùng của máy bay trở khángđược biết đến để được thường xuyên của tải (ZA-ZB-ZC-ZD).Phần trước cho thấy làm thế nào không hướng bù đắpMHO đặc trưng là vốn có thể hoạt động cho đóng-upZero lỗi điện áp, nơi sẽ có không có điện áp polarisingđể cho phép hoạt động của một yếu tố hướng đồng bằng mho. Một trong nhữngcách đảm bảo chính xác mho phản ứng yếu tố zero áplỗi là thêm một tỷ lệ phần trăm của điện áp từ các lành mạnhPhase(s) để điện áp polarising chính là một giai đoạn thay thếtài liệu tham khảo. Kỹ thuật này được gọi là cross-polarising, và nó cólợi thế của bảo tồn và thực sự tăng cường cáchướng tính chất của đặc tính mho. Bằng cách sử dụngmột giai đoạn điện áp bộ nhớ hệ thống, cung cấp một vài chu kỳ củaPre-lỗi điện áp tham chiếu trong một lỗi, cross-polarisation kỹ thuật cũng là hiệu quả nhất close-up ba phalỗi. Đối với loại lỗi, không có áp khỏe mạnh phatài liệu tham khảo có sẵn.
đang được dịch, vui lòng đợi..
Kết quả (Việt) 2:[Sao chép]
Sao chép!
It can be observed in Figure 11.11 how the load area is defined
according to a minimum impedance arc, constrained by
straight lines which emanate from the origin, 0. Modem
numerical relays typically do not use lenticular characteristic
shaping, but instead use load encroachment (load blinder)
detection. This allows a full mho characteristic to be used, but
with tripping prevented in the region of the impedance plane
known to be frequented by load (ZA-ZB-ZC-ZD).

The previous section showed how the non-directional offset
mho characteristic is inherently able to operate for close-up
zero voltage faults, where there would be no polarising voltage
to allow operation of a plain mho directional element. One
way of ensuring correct mho element response for zero-voltage
faults is to add a percentage of voltage from the healthy
phase(s) to the main polarising voltage as a substitute phase
reference. This technique is called cross-polarising, and it has
the advantage of preserving and indeed enhancing the
directional properties of the mho characteristic. By the use of
a phase voltage memory system, that provides several cycles of
pre-fault voltage reference during a fault, the cross-
polarisation technique is also effective for close-up three-phase
faults. For this type of fault, no healthy phase voltage
reference is available.
đang được dịch, vui lòng đợi..
 
Các ngôn ngữ khác
Hỗ trợ công cụ dịch thuật: Albania, Amharic, Anh, Armenia, Azerbaijan, Ba Lan, Ba Tư, Bantu, Basque, Belarus, Bengal, Bosnia, Bulgaria, Bồ Đào Nha, Catalan, Cebuano, Chichewa, Corsi, Creole (Haiti), Croatia, Do Thái, Estonia, Filipino, Frisia, Gael Scotland, Galicia, George, Gujarat, Hausa, Hawaii, Hindi, Hmong, Hungary, Hy Lạp, Hà Lan, Hà Lan (Nam Phi), Hàn, Iceland, Igbo, Ireland, Java, Kannada, Kazakh, Khmer, Kinyarwanda, Klingon, Kurd, Kyrgyz, Latinh, Latvia, Litva, Luxembourg, Lào, Macedonia, Malagasy, Malayalam, Malta, Maori, Marathi, Myanmar, Mã Lai, Mông Cổ, Na Uy, Nepal, Nga, Nhật, Odia (Oriya), Pashto, Pháp, Phát hiện ngôn ngữ, Phần Lan, Punjab, Quốc tế ngữ, Rumani, Samoa, Serbia, Sesotho, Shona, Sindhi, Sinhala, Slovak, Slovenia, Somali, Sunda, Swahili, Séc, Tajik, Tamil, Tatar, Telugu, Thái, Thổ Nhĩ Kỳ, Thụy Điển, Tiếng Indonesia, Tiếng Ý, Trung, Trung (Phồn thể), Turkmen, Tây Ban Nha, Ukraina, Urdu, Uyghur, Uzbek, Việt, Xứ Wales, Yiddish, Yoruba, Zulu, Đan Mạch, Đức, Ả Rập, dịch ngôn ngữ.