Page 101 of 149 Report No. 3302408.51
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
closing mechanism energized with 85% at the rated
Uc: (V)
N/A
The circuit-breaker is mounted complete on its own
support or an equivalent support.
P
Test made in free air: P
Distances of the metallic screen’s: (all sides) Up / Down: 60 mm
Left / Right: 5 mm
Front / Back: 0 mm
P
The characteristics of the metallic screen:
- woven wire mesh N/A
- perforated metal P
- expanded metal N/A
- ratio hole area/total area: 0,45-0,65 P
- size of hole: <30mm2 P
- finish: bare or conductive plating P
Test made in specified individual enclosure:
Details of these tests, including the dimensions of
the enclosure:
N/A
Fuse ”F”:
copper wire: diameter 0,8 mm, 50 mm long
P
Circuit is earthed at: (load-star- or supply-star point) Load-star P
Conductor cross-sectional area (mm²) : 185 mm2 x 2 P
If terminals unmarked:
line connected at: (underside /upside)
underside P
Tightening, torques: (Nm) 50 Nm P
Test sequence of operation: O – t – CO P
- test voltage U/Ue = 1,05 (V) .................... L1-L2:
..................................................................... L2-L3:
..................................................................... L3-L1:
466 V
466 V
466 V
P
- r.m.s. test current AC/DC: (A) ........................ L1:
.......................................................................... L2:
.......................................................................... L3:
42,8 kA
42,7 kA
42,6 kA
P
power factor/time constant : 0,25 P
- Factor ”n” 2,1 P
Page 102 of 149 Report No. 3302408.51
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
- peak test current (Amax) : 90,1 kA P
Test sequence ”O”
- max. let-through current: (kApeak) ................. L1:
.......................................................................... L2:
.......................................................................... L3:
16,5 kA
32,1 kA
20,6 kA
P
- Joule integral I²dt (A²s) ................................... L1:
.......................................................................... L2:
.......................................................................... L3:
700 kA2s
2,34 MA2s
822 kA2s
P
Pause, t: (min) 3 min P
Test sequence ”CO”
- max. let-through current: (kApeak) ................. L1:
.......................................................................... L2:
.......................................................................... L3:
19,6 kA
20,3 kA
32,5 kA
P
- Joule integral I²dt (A²s) ................................... L1:
.......................................................................... L2:
.......................................................................... L3:
1,3 MA2s
1,66 MA2s
2,28 MA2s
P
Melting of the fusible element No melting P
Holes in the PE-sheet for test sequence ”O” No hole P
Cracks observed No crack P
8.3.5.3 Verification of dielectric withstand
- equal to twice the rated operational voltage with a
minimum of 1000 V for 5 seconds
1000 V / 5 s P
- no breakdown or flashover P
- the leaking current for circuit-breaker suitable for
isolation: (<6mA / 1,1 Ue)
………………………………………………………L1:
………………………………………………………L2:
………………………………………………………L3:
………………………………………………………N:
484 V
0,04 mA
0,02 mA
0,06 mA
P
8.3.5.4 Verification of overload releases
The operation of overload releases shall be verified at 2,5 times the value of their
current setting on each pole separately.
The operating time shall not exceed the max. value stated by the manufacturer for
twice the current setting at the reference temperature, on a pole singly
Time specified by the manufacturer: tripping time ≤ 180 s P
Page 103 of 149 Report No. 3302408.51
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
- Operation time: (s) ......................................... L1:
.......................................................................... L2:
.......................................................................... L3:
31 s
29 s
32 s
P
Page 104 of 149 Report No. 3302408.51
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
8.3.5 TEST SEQUENCE III (Icu)
EasyPact CVS400F, electronic type, 3 poles, 400 A
Rated ultimate short-circuit breaking
Except where the combined test sequence applies, this test sequence applies to
circuit-breaker of utilization category A and to circuit-breaker of utilization B having a
rated ultimate short-circuit breaking capacity higher than the rated short-time
withstand current.
For circuit-breakers of utilization B having a rated short-time withstand current equal
to their rated ultimate short-circuit breaking capacity, this test sequence need not be
made, since, in this case, the ultimate short-circuit breaking capacity, is verified when
carrying out test sequence IV.
For integrally fused circuit-breakers, test sequence V applies in place of this
sequence.
Type designation or serial number EasyPact CVS400F
Sample no: #50
Rated current: In (A) 400 A
Rated operational voltage: Ue (V) 240 V
Rated ultimate short-circuit breaking capacity: (kA) 40 kA, tested at 70 kA
Rated control supply voltage of closing mechanism:
Uc (V)
N/A
Rated control supply voltage of shunt release:
Uc (V)
N/A
This test sequence need not be made when Icu = Ics
8.3.5.1 The operation of overload releases shall be verified at twice the value of their
current setting on each pole separately.
The operating time shall not exceed the max. value stated by the manufacturer for
twice the current setting at the reference temperature, on a pole singly
Time specified by the manufacturer: 50 s ≤ tripping time ≤ 180 s P
- Operation time: (s) ......................................... L1:
.......................................................................... L2:
.......................................................................... L3:
50 s
53 s
58 s
P
8.3.5.2 Test of rated ultimate short-circuit breaking capacity
The test sequence of operations is O – t – CO
For circuit-breaker fitted with adjustable releases,
test shall be made with the current and time settings
at maximum.
P
Page 105 of 149 Report No. 3302408.51
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
closing mechanism energized with 85% at the rated
Uc: (V)
N/A
The circuit-breaker is mounted complete on its own
support or an equivalent support.
P
Test made in free air: P
Distances of the metallic screen’s: (all sides) Up / Down: 60 mm
Left / Right: 5 mm
Front / Back: 0 mm
P
The characteristics of the metallic screen:
- woven wire mesh N/A
- perforated metal P
- expanded metal N/A
- ratio hole area/total area: 0,45-0,65 P
- size of hole: <30mm2 P
- finish: bare or conductive plating P
Test made in specified individual enclosure:
Details of these tests, including the dimensions of
the enclosure:
N/A
Fuse ”F”:
copper wire: diameter 0,8 mm, 50 mm long
P
Circuit is earthed at: (load-star- or supply-star point) Load-star P
Conductor cross-sectional area (mm²) : 240 mm2 P
If terminals unmarked:
line connected at: (underside /upside)
upside P
Tightening, torques: (Nm) 50 Nm P
Test sequence of operation: O – t – CO P
- test voltage U/Ue = 1,05 (V) .................... L1-L2:
..................................................................... L2-L3:
..................................................................... L3-L1:
258 V
258 V
258 V
P
- r.m.s. test current AC/DC: (A) ........................ L1:
.......................................................................... L2:
.......................................................................... L3:
70,8 kA
70,7 kA
70,0 kA
P
power factor/time constant : 0,2 P
- Factor ”n” 2,2