117Function assignment of externalterminal and control4PARAMETERS(2) R dịch - 117Function assignment of externalterminal and control4PARAMETERS(2) R Việt làm thế nào để nói

117Function assignment of externalt


117
Function assignment of external
terminal and control
4
PARAMETERS
(2) Response time of each signal

The response time of the X10 signal is within 2ms. However, when the X10 signal is not assigned at the
Pr. 30
Regenerative function selection
setting of "2" (FR-HC/MT-HC/FR-CV connection), the response time of the MRS
signal is within 2ms.
Pr. 17 MRS input selection
is made invalid.
4.10.2 Inverter output shutoff signal (MRS signal, Pr. 17)
Pr. 30
Setting
MRS
Assignment
X10
Assignment
Response Time
Pr. 17
MRS
X10
2
{
×
Within 2ms

Invalid
×
{

Within 2ms

{{
Within 20ms Within 2ms Valid
Other than 2
{
×
Within 20ms

Valid
×
{
⎯⎯⎯
{{
Within 20ms

Valid
The inverter output can be shut off from the MRS signal. The logic of the MRS signal can also be selected.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
17 MRS input selection
0
0 Open input always
2 Close input always (NC contact input specifications)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
(Refer to page 175)
(1) Output shutoff signal (MRS signal)

Turning on the output shutoff signal (MRS) during inverter running
shuts off the output immediately.

Terminal MRS may be used as described below.
(a) When mechanical brake (e.g. el
ectromagnetic brake) is used to
stop motor
The inverter output is shut off when the mechanical brake
operates.
(b) To provide interlock to disable operation by the inverter
With the MRS signal on, the inverter cannot be operated if the
start signal is entered into the inverter.
(c) Coast the motor to a stop.
When the start signal is turned off, the inverter decelerates the
motor to a stop in the preset deceleration time, but when the MRS
signal is turned on, the motor coasts to a stop.
(2) MRS signal logic inversion
(Pr. 17)

When
Pr. 17
is set to "2", the MRS signal (output stop) can be
changed to the normally closed (NC contact) input specification.
When the MRS signal turns on (opens), the inverter shuts off the
output.
REMARKS

The MRS signal is assigned to the terminal MRS in the initial setting. By setting "24" in any of
Pr. 178 to Pr. 189 (input terminal
function selection)
, the RT signal can be assigned to the other terminal.

The MRS signal can shut off the output, independently of the PU, external or network operation mode.
CAUTION

Changing the terminal assignment using
Pr. 178 to Pr. 189 (input terminal function selection)
may affect the other functions. Please
make setting after confirming the function of each terminal.

Parameters referred to

Pr. 178 to Pr. 189 (Input terminal function selection) Refer to page 115
ON
ON
MRS signal
STF (STR)
signal
Motor coasts
to stop
Time
(Initial
value)
Output
stop
Output
stop
MRS
Inverter
MRS
Inverter
Setting value "0"
Setting value "2"
SD SD
118
Function assignment of external
terminal and control
4.10.3 Condition selection of function validit
y by the second function selection signal
(RT) (RT signal, Pr. 155)

When the RT signal turns on, the second function becomes valid.

The second function has the following applications.
(a) Switching between normal use and emergency use
(b) Switching between heavy load and light load
(c) Changing of acceleration/deceleration time by broken line acceleration/deceleration
(d) Switching of characteristic between main motor and sub motor

Functions that can be set as second functions
You can select the second function using the external terminal (RT signal).
You can also set the RT signal operation condition (reflection time).
Parameter
Number
Name
Initial Value
Setting Range
Description
155
RT signal function validity
condition selection
0
0
Second function is immediately valid with on of the
RT signal.
10
Second function is valid only during the RT siganl is
on and constant speed operation.
(invalid during acceleration/deceleration)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
(Refer to page 175)
Second function
connection diagram
Second acceleration/deceleration time example
Function
First Function
Parameter Number
Second Function
Parameter Number
Refer to
Page
Torque boost Pr. 0 Pr. 46 74
Base Frequency Pr. 3 Pr. 47 84
Acceleration time Pr. 7 Pr. 44 96
Deceleration time Pr. 8 Pr. 44, Pr. 45 96
Electronic thermal relay function Pr. 9 Pr. 51 101
Stall prevention Pr. 22 Pr. 48, Pr. 49 77
Output frequency detection Pr. 42(Pr. 43) Pr. 50 125
REMARKS

The RT signal is assigned to the RT terminal in the initial setting. By setting "3" in any of
Pr. 178 to Pr. 189 (input terminal function
selection)
, the RT signal can be assigned to the other terminal.

When the RT signal is on, the other functions such as the second acceleration/deceleration time are also selected.
CAUTION

Changing the terminal assignment using
Pr. 178 to Pr. 189 (input terminal function selection)
may affect the other functions. Please
make setting after confirming the function of each terminal.

Parameters referred to

Pr. 178 to Pr.189 (input terminal function selection) Refer to page 115
STF(STR)
Inverter
Start
Second
function
selection
RT
High speed
RH
Middle speed
RM
SD
(initial value)
RT
Output frequency
Setting value "0"
RH
RM
Acceleration
time is reflected
Time
119
Function assignment of external
terminal and control
4
PARAMETERS
4.10.4 Start signal selection (STF, STR, STOP signal, Pr. 250)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
(Refer to page 175)
(1) 2-wire type (STF, STR signal)

A two-wire type connection is shown below.

In the initial setting, the forward/reverse rotation signals (STF/STR) are used as start and stop signals. Turn on
either of the forward and reverse rotation signals to start
the motor in the corresponding direction. If both are turned
off (or on) during operation, the inverter decelerates to a stop.

The speed setting signal may either be given by entering
0 to 10VDC across the speed setting input terminal 2-5,
by setting the required values in
Pr. 4 to Pr. 6 Multi-speed setting (high, middle, low speeds)
, etc. (For multi-speed
operation, refer to
page 88
)

When
Pr. 250
is set in any of "1000 to 1100, 8888", the STF signal becomes a start command and the STR signal a
forward/reverse command.
You can select the operation of the start signal (STF/STR).
Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns off.
Used to stop the motor with a mechanical brake, etc. together with switching off of the start signal.
(Refer to
page 112
for stop selection)
Parameter
Number
Name
Initial
Value
Setting
Range
Description
Start Signal (STF/STR)
Stop Operation
(Refer to page 112)
250 Stop selection
9999
0 to 100s
STF signal: Forward rotation
start
STR signal: Reverse rotation
start
The motor is coasted to a stop
when the preset time elapses
after the start signal is turned
off. When the setting is any of
1000s to 1100s, the inverter
coasts to a stop in (
Pr. 250
-
1000)s.
1000s to
1100s
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
9999
STF signal: Forward rotation
start
STR signal: Reverse rotation
start
When the start signal is turned
off, the motor decelerates to
stop.
8888
STF signal: Start signal
STR signal: Forward/reverse
rotation signal
2-wire connection example (
Pr. 250
= "9999")
2-wire connection example (
Pr. 250
= "8888")
REMARKS

When
Pr. 250
is set in any of "0 to 100, 1000 to 1100", the motor coasts to a stop if the start command is turned off.
(Refer to page
112)

The STF and STR signals are assigned to the STF and STR terminals in the initial setting. The STF signal can be assigned to
Pr. 178 STF terminal function selection
and the STR signal to
Pr. 179 STR terminal function selection
only.
Forward
rotation start
Reverse
rotation start
STF
ON
Time
STF
STR
Inverter
Output frequency
ON
STR
10
2
5
Forward
rotation
Reverse
rotation
SD
Start signal
Forward/
reverse
signal
STF
Time
STF
STR
Inverter
Output frequency
STR
10
2
5
Forward
rotation
Reverse
rotation
ON
ON
SD
120
Function assignment of external
terminal and control
(2) 3-wire type (STF, STR, STOP signal)

A 3-wire type connection is shown below.

The start self-holding selection becomes valid when the STOP
signal is turned on. In this case, the forward/reverse
rotation signal functions only as a start signal.

If the start signal (STF or STR) is turned on and then of
f, the start signal is held and makes a start. When changing
the direction of rotation, turn STR (STF) on once and then off.

To stop the inverter, turning off the STOP signal once decelerates it to a stop.
(3) Start signal selection
3-Wire Type Connection Example (
Pr. 250
="9999")
3-Wire Type Connection Example (
Pr. 250
="8888")
REMARKS

The STOP signal is assigned to the terminal STOP in the initial setting. By setting "25" in
Pr. 178 to Pr. 189
, the STOP signal can
also be assigned to the other terminal.

When the JOG signal is turned on to enable jog operation, the STOP signal becomes invalid.

If the MRS signal is turned on to stop the output, the self-holding function is not canceled.
STF
STR
Pr. 250
Setting Inverter Status
0 to 100s, 9999
1000
0/5000
Từ: -
Sang: -
Kết quả (Việt) 1: [Sao chép]
Sao chép!
117Chức năng nhiệm vụ của bên ngoàithiết bị đầu cuối và kiểm soát4THAM SỐ(2) phản ứng thời gian của mỗi tín hiệu⋅Thời gian phản ứng của X 10 tín hiệu nằm 2ms. Tuy nhiên, khi X 10 tín hiệu không được chỉ định tại các PR. 30Lựa chọn chức năng tái tạo thiết lập của "2" (FR-HC/MT-HC/FR-CV kết nối), thời gian phản ứng của MRStín hiệu nằm 2ms. Lựa chọn đầu vào PR. 17 MRS được thực hiện không hợp lệ.4.10.2 biến tần đầu ra tín hiệu ngắt (MRS tín hiệu, PR 17)PR. 30Thiết lậpBÀ Chuyển nhượngX 10 Chuyển nhượngThời gian đáp ứngPR. 17BÀX 102{×Trong vòng 2ms⎯Không hợp lệ×{⎯Trong vòng 2ms⎯{{Trong vòng 20ms trong 2ms hợp lệKhác hơn 2{×Trong vòng 20ms⎯Hợp lệ×{⎯⎯⎯{{Trong vòng 20ms⎯Hợp lệSản lượng biến có thể được tắt từ tín hiệu MRS. Logic của tín hiệu MRS cũng có thể được lựa chọn.Tham số SốTênBan đầu Giá trịThiết lập Phạm viMô tả17 MRS lựa chọn đầu vào00 mở đầu vào luôn luôn2 đóng nhập luôn luôn (NC liên hệ vào thông số kỹ thuật)Các thông số trên có thể được thiết lập khi Nhóm PR. 160 người dùng đọc lựa chọn = "0". (Hãy tham khảo trang 175)(1) đầu ra tín hiệu ngắt (MRS tín hiệu)⋅Bật ra tín hiệu ngắt (MRS) trong biến tần chạytắt đầu ra ngay lập tức.⋅Thiết bị đầu cuối bà có thể được sử dụng như mô tả dưới đây.(a) khi cơ khí phanh (ví dụ như electromagnetic phanh) là được sử dụng đểngừng động cơSản lượng biến tần tắt khi cơ khí phanhhoạt động.(b) To provide interlock to disable operation by the inverterWith the MRS signal on, the inverter cannot be operated if thestart signal is entered into the inverter.(c) Coast the motor to a stop. When the start signal is turned off, the inverter decelerates themotor to a stop in the preset deceleration time, but when the MRSsignal is turned on, the motor coasts to a stop.(2) MRS signal logic inversion (Pr. 17)⋅When Pr. 17 is set to "2", the MRS signal (output stop) can bechanged to the normally closed (NC contact) input specification.When the MRS signal turns on (opens), the inverter shuts off theoutput.REMARKS⋅The MRS signal is assigned to the terminal MRS in the initial setting. By setting "24" in any of Pr. 178 to Pr. 189 (input terminalfunction selection), the RT signal can be assigned to the other terminal.⋅The MRS signal can shut off the output, independently of the PU, external or network operation mode.CAUTION⋅Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Pleasemake setting after confirming the function of each terminal.♦ Parameters referred to ♦Pr. 178 to Pr. 189 (Input terminal function selection) Refer to page 115ONONMRS signalSTF (STR) signalMotor coasts to stopTime(Initial value)Output stopOutput stopMRSInverterMRSInverterSetting value "0"Setting value "2"SD SD118Function assignment of external terminal and control4.10.3 Condition selection of function validity by the second function selection signal (RT) (RT signal, Pr. 155)⋅When the RT signal turns on, the second function becomes valid.⋅The second function has the following applications.(a) Switching between normal use and emergency use(b) Switching between heavy load and light load(c) Changing of acceleration/deceleration time by broken line acceleration/deceleration(d) Switching of characteristic between main motor and sub motor⋅Functions that can be set as second functionsYou can select the second function using the external terminal (RT signal).You can also set the RT signal operation condition (reflection time).Parameter NumberNameInitial ValueSetting RangeDescription155RT signal function validity condition selection00Second function is immediately valid with on of the RT signal.10Second function is valid only during the RT siganl is on and constant speed operation. (invalid during acceleration/deceleration)The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 175)Second function connection diagramSecond acceleration/deceleration time exampleFunctionFirst Function Parameter NumberSecond Function Parameter NumberRefer to PageTorque boost Pr. 0 Pr. 46 74Base Frequency Pr. 3 Pr. 47 84Acceleration time Pr. 7 Pr. 44 96Deceleration time Pr. 8 Pr. 44, Pr. 45 96Electronic thermal relay function Pr. 9 Pr. 51 101Stall prevention Pr. 22 Pr. 48, Pr. 49 77Output frequency detection Pr. 42(Pr. 43) Pr. 50 125REMARKS⋅The RT signal is assigned to the RT terminal in the initial setting. By setting "3" in any of Pr. 178 to Pr. 189 (input terminal functionselection), the RT signal can be assigned to the other terminal.⋅When the RT signal is on, the other functions such as the second acceleration/deceleration time are also selected.CAUTION⋅Changing the terminal assignment using Pr. 178 to Pr. 189 (input terminal function selection) may affect the other functions. Pleasemake setting after confirming the function of each terminal.♦ Parameters referred to ♦Pr. 178 to Pr.189 (input terminal function selection) Refer to page 115STF(STR)InverterStartSecond function selectionRTHigh speedRHMiddle speedRMSD(initial value)RTOutput frequencySetting value "0"RHRMAcceleration time is reflectedTime119Function assignment of externalterminal and control4PARAMETERS4.10.4 Start signal selection (STF, STR, STOP signal, Pr. 250)The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 175)(1) 2-wire type (STF, STR signal)⋅A two-wire type connection is shown below.⋅In the initial setting, the forward/reverse rotation signals (STF/STR) are used as start and stop signals. Turn oneither of the forward and reverse rotation signals to start the motor in the corresponding direction. If both are turnedoff (or on) during operation, the inverter decelerates to a stop.⋅The speed setting signal may either be given by entering 0 to 10VDC across the speed setting input terminal 2-5,by setting the required values in Pr. 4 to Pr. 6 Multi-speed setting (high, middle, low speeds), etc. (For multi-speedoperation, refer to page 88)⋅When Pr. 250 is set in any of "1000 to 1100, 8888", the STF signal becomes a start command and the STR signal aforward/reverse command.You can select the operation of the start signal (STF/STR).Used to select the stopping method (deceleration to a stop or coasting) when the start signal turns off.Used to stop the motor with a mechanical brake, etc. together with switching off of the start signal.(Refer to page 112 for stop selection)Parameter NumberNameInitial ValueSetting RangeDescriptionStart Signal (STF/STR)Stop Operation(Refer to page 112)250 Stop selection99990 to 100sSTF signal: Forward rotation startSTR signal: Reverse rotation startThe motor is coasted to a stop when the preset time elapses after the start signal is turned off. When the setting is any of 1000s to 1100s, the inverter coasts to a stop in (Pr. 250 - 1000)s.1000s to 1100sSTF signal: Start signalSTR signal: Forward/reverse rotation signal9999STF signal: Forward rotation startSTR signal: Reverse rotation startWhen the start signal is turned off, the motor decelerates to stop.8888STF signal: Start signalSTR signal: Forward/reverse rotation signal2-wire connection example (Pr. 250 = "9999")2-wire connection example (Pr. 250 = "8888")REMARKS⋅When Pr. 250 is set in any of "0 to 100, 1000 to 1100", the motor coasts to a stop if the start command is turned off. (Refer to page112)⋅The STF and STR signals are assigned to the STF and STR terminals in the initial setting. The STF signal can be assigned toPr. 178 STF terminal function selection and the STR signal to Pr. 179 STR terminal function selection only.Forward rotation startReverse rotation startSTFONTimeSTFSTRInverterOutput frequencyONSTR1025Forward rotationReverse rotationSDStart signalForward/reverse signalSTFTimeSTFSTRInverterOutput frequencySTR1025Forward rotationReverse rotationONONSD120Function assignment of external terminal and control(2) 3-wire type (STF, STR, STOP signal)⋅A 3-wire type connection is shown below.⋅The start self-holding selection becomes valid when the STOP signal is turned on. In this case, the forward/reverserotation signal functions only as a start signal.⋅If the start signal (STF or STR) is turned on and then off, the start signal is held and makes a start. When changingthe direction of rotation, turn STR (STF) on once and then off.⋅To stop the inverter, turning off the STOP signal once decelerates it to a stop.(3) Start signal selection3-Wire Type Connection Example (Pr. 250 ="9999")3-Wire Type Connection Example (Pr. 250 ="8888")REMARKS⋅The STOP signal is assigned to the terminal STOP in the initial setting. By setting "25" in Pr. 178 to Pr. 189, the STOP signal can also be assigned to the other terminal.⋅When the JOG signal is turned on to enable jog operation, the STOP signal becomes invalid.⋅If the MRS signal is turned on to stop the output, the self-holding function is not canceled.STFSTRPr. 250 Setting Inverter Status0 to 100s, 99991000
đang được dịch, vui lòng đợi..
Kết quả (Việt) 2:[Sao chép]
Sao chép!

117
Chức năng nhiệm vụ của bên ngoài
thiết bị đầu cuối và kiểm soát
4
SỐ
(2) Thời gian đáp ứng của mỗi tín hiệu

Thời gian đáp ứng của tín hiệu X10 là trong 2ms. Tuy nhiên, khi các tín hiệu X10 không được phân định tại
Pr. 30
lựa chọn chức năng tái tạo
khung cảnh của "2" (FR-HC / MT-HC / kết nối FR-CV), thời gian phản ứng của MRS
tín hiệu nằm trong 2ms.
Pr. Lựa chọn đầu vào 17 MRS
được thực hiện không hợp lệ.
4.10.2 Inverter tín hiệu đầu ra ngắt (tín hiệu MRS, 17 Pr.)
Pr. 30
Thiết
MRS
Phân
X10
Phân
Thời gian đáp ứng
Pr. 17
MRS
X10
2
{
×
Trong 2ms

không hợp lệ
×
{

Trong 2ms

{{
Trong vòng 20ms Trong 2ms hợp lệ
khác hơn 2
{
×
Trong vòng 20ms

Valid
×
{
⎯⎯⎯
{{
Trong vòng 20ms

Valid
Các đầu ra biến tần có thể được tắt từ tín hiệu MRS. Logic của tín hiệu MRS cũng có thể được lựa chọn.
Parameter
Số
Tên
Initial
Value
Setting
đun
Mô tả
17 MRS lựa chọn đầu vào
0
0 mở đầu vào luôn
2 Close đầu vào luôn (NC thông số kỹ thuật đầu vào liên lạc)
Các thông số trên có thể được thiết lập khi
Pr. 160 Nhóm người dùng lựa chọn đọc
= "0".
(Tham khảo trang 175)
(1) Tín hiệu đầu ra ngắt (tín hiệu MRS)

Bật tín hiệu đầu ra ngắt (MRS) trong biến tần chạy
tắt đầu ra ngay lập tức.

ga MRS có thể sử dụng như mô tả dưới đây.
(a) Khi cơ khí phanh (ví dụ như el
phanh ectromagnetic) được sử dụng để
ngăn chặn động cơ
Các đầu ra biến tần được tắt khi phanh cơ khí
hoạt động.
(b) Để cung cấp khóa liên động để vô hiệu hóa hoạt động của biến tần
với tín hiệu MRS trên, biến tần không thể hoạt động nếu các
tín hiệu bắt đầu được nhập vào biến tần.
(c) Coast động cơ dừng lại.
Khi tín hiệu bắt đầu tắt, biến tần giảm tốc của
động cơ đến một điểm dừng trong thời gian giảm tốc cài sẵn, nhưng khi MRS
tín hiệu được bật, motor dừng lại.
(2) tín hiệu MRS lý đảo ngược
(Pr. 17)

Khi
Pr. 17
được thiết lập để "2", các tín hiệu MRS (output stop) có thể được
thay đổi để thường đóng (NC liên lạc) đặc điểm kỹ thuật đầu vào.
Khi tín hiệu MRS lượt về (mở), biến tần tắt các
đầu ra.
CHÚ

MRS tín hiệu được gán cho các thiết bị đầu cuối MRS trong các thiết lập ban đầu. Bằng cách thiết lập "24" trong bất kỳ của
Pr. 178 để PR. 189 (đầu vào thiết bị đầu cuối
lựa chọn chức năng)
, các tín hiệu RT có thể được gán cho các thiết bị đầu cuối khác.

Các tín hiệu MRS có thể tắt các đầu ra, độc lập với PU, chế độ hoạt động bên ngoài hoặc mạng.
CAUTION

Thay đổi giao thiết bị đầu cuối sử dụng
Pr. 178 để PR. 189 (đầu vào lựa chọn chức năng đầu cuối)
có thể ảnh hưởng đến các chức năng khác. Hãy
làm cho thiết lập sau khi xác nhận các chức năng của từng thiết bị đầu cuối.

Các thông số gọi

Pr. 178 để PR. 189 (Input Terminal lựa chọn chức năng) Hãy tham khảo trang 115
ON
ON
tín hiệu MRS
STF (STR)
tín hiệu
bờ biển xe
dừng
Time
(Initial
value)
Output
dừng
Output
ngừng
MRS
Inverter
MRS
Inverter
Thiết lập giá trị "0"
Thiết lập giá trị "2"
SD SD
118
phân công chức năng bên ngoài
thiết bị đầu cuối và kiểm soát
lựa chọn 4.10.3 Điều kiện của chức năng validit
y bởi các tín hiệu lựa chọn chức năng thứ hai
(RT) (tín hiệu RT, Pr. 155)

Khi tín hiệu RT bật, chức năng thứ hai có hiệu lực.

thứ hai chức năng có các ứng dụng sau đây.
(a) Chuyển đổi giữa việc sử dụng bình thường và sử dụng khẩn cấp
(b) Chuyển đổi giữa tải nặng và tải nhẹ
(c) Thay đổi thời gian tăng / giảm tốc do vỡ đường tăng / giảm tốc
(d) chuyển mạch của đặc trưng giữa động cơ chính và động cơ phụ

Chức năng có thể được thiết lập như là chức năng thứ hai
Bạn có thể chọn chức năng thứ hai bằng cách sử dụng thiết bị đầu cuối bên ngoài (RT tín hiệu).
Bạn cũng có thể thiết lập các điều kiện hoạt động tín hiệu RT (thời gian phản ánh).
Thông số
Số
Tên
Giá trị ban đầu
Thiết đun
Mô tả
155
chức năng tín hiệu giá trị RT
lựa chọn điều kiện
0
0
Chức năng thứ hai là ngay lập tức có giá trị với trên các
tín hiệu RT.
10
chức năng thứ hai là chỉ có hiệu lực trong thời gian Tín hiệu quang RT là
trên và tốc độ hoạt động liên tục.
(không hợp lệ trong thời gian tăng / giảm tốc)
Các thông số trên có thể được thiết lập khi
Pr. 160 Nhóm người dùng lựa chọn đọc
= "0".
(Tham khảo trang 175)
Thứ hai chức năng
sơ đồ kết nối
thứ hai tăng tốc / thời gian giảm tốc dụ
Function
Chức năng đầu tiên
Thông số Số
Thứ hai chức năng
Thông số Số
Tham khảo
trang
Torque tăng Pr. 0 Pr. 46 74
Cơ sở Tần số Pr. 3 Pr. 47 84
Acceleration thời Pr. 7 Pr. 44 96
giảm tốc thời gian Pr. 8 Pr. 44, Pr. 45 96
điện tử chức năng rơle nhiệt Pr. 9 Pr. 51 101
Stall phòng Pr. 22 Pr. 48, Pr. 49 77
Output phát hiện tần số Pr. 42 (Pr. 43) Pr. 50 125
NHẬN XÉT

Các tín hiệu RT được gán cho các thiết bị đầu cuối RT trong các thiết lập ban đầu. Bằng cách thiết lập "3" trong bất kỳ của
Pr. 178 để PR. 189 (đầu vào chức năng đầu cuối
lựa chọn)
, tín hiệu RT có thể được gán cho các thiết bị đầu cuối khác.

Khi tín hiệu RT là ngày, các chức năng khác như thời gian tăng tốc / giảm tốc thứ hai cũng được chọn.
CAUTION

Thay đổi giao thiết bị đầu cuối sử dụng
Pr . 178 để PR. 189 (đầu vào lựa chọn chức năng đầu cuối)
có thể ảnh hưởng đến các chức năng khác. Hãy
làm cho thiết lập sau khi xác nhận các chức năng của từng thiết bị đầu cuối.

Các thông số gọi

Pr. 178 Pr.189 (đầu vào thiết bị đầu cuối lựa chọn chức năng) Hãy tham khảo trang 115
STF (STR)
Inverter
Bắt đầu
Thứ hai
chức năng
lựa chọn
RT
tốc độ cao
RH
tốc Trung
RM
SD
(giá trị ban đầu)
RT
Tần số ra
giá trị Setting "0"
RH
RM
Acceleration
thời gian được phản ánh
Time
119
Chức năng nhiệm vụ của bên ngoài
thiết bị đầu cuối và kiểm soát
4
THÔNG SỐ
4.10.4 lựa chọn tín hiệu Start (STF, STR, STOP tín hiệu, Pr. 250)
Các thông số trên có thể được thiết lập khi
Pr. 160 Nhóm người dùng lựa chọn đọc
= "0".
(Tham khảo trang 175)
(1) loại 2-dây (STF, tín hiệu STR)

Một loại kết nối hai dây được hiển thị dưới đây.

Trong các thiết lập ban đầu, thuận / ngược tín hiệu xoay (STF / STR) được sử dụng như bắt đầu và dừng lại tín hiệu. Bật
một trong hai phía trước và ngược tín hiệu quay để bắt đầu
các động cơ theo hướng tương ứng. Nếu cả hai được bật
tắt (hoặc trên) trong khi hoạt động, biến tần giảm tốc để dừng lại.

Các tín hiệu thiết lập tốc độ có thể được đưa ra bằng cách nhập
từ 0 đến 10VDC qua các thiết bị đầu cuối đầu vào thiết lập tốc độ 2-5,
bằng cách thiết lập các giá trị cần thiết trong
Pr . 4 để Pr. 6 thiết lập nhiều cấp tốc độ (cao, trung bình, tốc độ thấp)
, vv (Đối với đa tốc độ
hoạt động, tham khảo
trang 88
)

Khi
Pr. 250
được đặt trong bất kỳ "1000-1100, 8888", các tín hiệu STF trở thành một lệnh bắt đầu và STR báo hiệu một
lệnh chuyển tiếp / ngược lại.
Bạn có thể chọn các hoạt động của các tín hiệu bắt đầu (STF / STR).
Được sử dụng để chọn Phương pháp dừng (giảm tốc để dừng hoặc xuống dốc) khi tín hiệu bắt đầu tắt.
Được sử dụng để ngăn chặn các động cơ với phanh cơ khí, vv cùng với ngắt của tín hiệu bắt đầu.
(Tham khảo
trang 112
để lựa chọn stop)
Thông số
Number
Name
Initial
Value
Setting
đun
Mô tả
Bắt đầu Signal (STF / STR)
Ngừng hoạt động
(tham khảo trang 112)
250 Dừng lựa chọn
9999
0 đến 100s
tín hiệu STF: Chuyển tiếp xoay
đầu
tín hiệu STR: Reverse xoay
bắt đầu
động cơ được coasted dừng lại
khi thời gian định sẵn trôi qua
sau khi các tín hiệu bắt đầu được bật
tắt. Khi cài đặt bất kỳ của
1000s đến 1100s, biến tần
bờ biển đến một điểm dừng trong (
Pr 250.
-
1000) s.
1000s đến
1100s
tín hiệu STF: Bắt đầu tín hiệu
tín hiệu STR: Chuyển tiếp / ngược lại
luân chuyển tín hiệu
9999
tín hiệu STF: Chuyển tiếp xoay
bắt đầu
STR tín hiệu: Reverse xoay
đầu
Khi tín hiệu bắt đầu được bật
ra, động cơ giảm tốc để
dừng lại.
8888
tín hiệu STF: Bắt đầu tín hiệu
tín hiệu STR: Chuyển tiếp / ngược lại
tín hiệu xoay
(2 dây ví dụ kết nối
. Pr 250
= "9999")
2-wire Ví dụ kết nối (
Pr. 250
= "8888")
CHÚ

Khi
Pr. 250
được đặt trong bất kỳ của "0-100, 1000-1100", các motor dừng lại nếu lệnh bắt đầu được tắt.
(Tham khảo trang
112)

Các STF và tín hiệu STR được giao cho STF và thiết bị đầu cuối STR trong các thiết lập ban đầu. Các tín hiệu STF có thể được gán cho
Pr. 178 STF lựa chọn chức năng thiết bị đầu cuối
và các tín hiệu STR để
Pr. 179 STR lựa chọn chức năng đầu cuối
chỉ.
Forward
xoay bắt đầu
Xếp
xoay bắt đầu
STF
ON
Time
STF
STR
Inverter
Tần số ngõ ra
ON
STR
10
2
5
Chuyển tiếp
xoay
ngược
xoay
SD
Bắt đầu tín hiệu
tiếp /
ngược lại
tín hiệu
STF
Time
STF
STR
Inverter
tần số đầu ra
STR
10
2
5
Chuyển tiếp
xoay
Xếp
xoay
ON
ON
SD
120
Chức năng nhiệm vụ của bên ngoài
thiết bị đầu cuối và kiểm soát
(2) loại 3-wire (STF, STR, STOP tín hiệu)

Một loại kết nối 3-wire được hiển thị dưới đây.

Việc lựa chọn tự cầm đầu có hiệu lực khi DỪNG
tín hiệu được bật. Trong trường hợp này, sự chuyển tiếp / ngược
chức năng tín hiệu xoay chỉ như là một tín hiệu bắt đầu.

Nếu tín hiệu start (STF hoặc STR) được bật và sau đó của
f, các tín hiệu bắt đầu được tổ chức và làm cho một sự khởi đầu. Khi thay đổi
chiều quay, biến STR (STF) trên một lần và sau đó đi.

Để ngăn chặn các biến tần, tắt tín hiệu STOP lần decelerates nó dừng lại.
(3) Bắt đầu lựa chọn tín hiệu
3-Wire Connection Type Ví dụ (
Pr . 250
= "9999")
3-Wire Connection Type Ví dụ (
Pr. 250
= "8888")
CHÚ

Các tín hiệu STOP được gán cho STOP thiết bị đầu cuối trong các thiết lập ban đầu. Bằng cách thiết lập "25" trong
Pr. 178 để PR. 189
, các tín hiệu STOP có thể
cũng được giao cho các thiết bị đầu cuối khác.

Khi tín hiệu JOG được bật để cho phép hoạt động chạy bộ, các tín hiệu STOP trở nên không hợp lệ.

Nếu tín hiệu MRS được bật để ngăn chặn đầu ra, tự giữ chức năng không được hủy bỏ.
STF
STR
Pr. 250
Setting Inverter Status
0 đến 100, 9999
1000
đang được dịch, vui lòng đợi..
 
Các ngôn ngữ khác
Hỗ trợ công cụ dịch thuật: Albania, Amharic, Anh, Armenia, Azerbaijan, Ba Lan, Ba Tư, Bantu, Basque, Belarus, Bengal, Bosnia, Bulgaria, Bồ Đào Nha, Catalan, Cebuano, Chichewa, Corsi, Creole (Haiti), Croatia, Do Thái, Estonia, Filipino, Frisia, Gael Scotland, Galicia, George, Gujarat, Hausa, Hawaii, Hindi, Hmong, Hungary, Hy Lạp, Hà Lan, Hà Lan (Nam Phi), Hàn, Iceland, Igbo, Ireland, Java, Kannada, Kazakh, Khmer, Kinyarwanda, Klingon, Kurd, Kyrgyz, Latinh, Latvia, Litva, Luxembourg, Lào, Macedonia, Malagasy, Malayalam, Malta, Maori, Marathi, Myanmar, Mã Lai, Mông Cổ, Na Uy, Nepal, Nga, Nhật, Odia (Oriya), Pashto, Pháp, Phát hiện ngôn ngữ, Phần Lan, Punjab, Quốc tế ngữ, Rumani, Samoa, Serbia, Sesotho, Shona, Sindhi, Sinhala, Slovak, Slovenia, Somali, Sunda, Swahili, Séc, Tajik, Tamil, Tatar, Telugu, Thái, Thổ Nhĩ Kỳ, Thụy Điển, Tiếng Indonesia, Tiếng Ý, Trung, Trung (Phồn thể), Turkmen, Tây Ban Nha, Ukraina, Urdu, Uyghur, Uzbek, Việt, Xứ Wales, Yiddish, Yoruba, Zulu, Đan Mạch, Đức, Ả Rập, dịch ngôn ngữ.