Dear Mr. Sơn Trang,Regarding about the Site Instruction you sent yesterday, the concealed conduits for the wall sockets must be installed from ceiling down to sockets instead of underfloor (as the mock-up room scene), although the basic design and approved shop drawings has been confirmed the way to install the conduits is underfloor.Due to the longer route to be fixed the conduits looped over the ceiling so the quantity of conduits and cables(power, LAN and telephone) will be increased so much compared with the original approved way under floor, with more than 1,000 pcs of power socket as well as more than 300 pcs of LAN and Telephone sockets of entire project is considering about the added conduits and cables quantity.Please take consideration for the AM material quantity increasing and advise TVT the VO to be applied.