1. Name of risk/Insured:1.1 Name: ITALON VIETNAM CO., LTD. ..................................................................................1.2 Nature of risk: Polyester yarn manufacturer ....................................................................................1.3 Location: Lot II2-3-4, My Xuan B1 IP, My Xuan, Tan Thanh, BRVT, Vietnam ........................ [10°38'44.3"N 107°03'43.2"E]...................................................................................1.4 Survey date: 28 Jul 2015 ............................................ Surveyor: Pham Dang Khoa ...................1.5 Contact: Peter Pan (Mr.) – Technical Manager ......................................................................2. General Information:2.1 When was the plant put into operation? 2011 ...............................................................................2.2 Which raw materials are used/finished products manufactured? (Describe briefly)- Nylon/polyester filament – POY (Partially Oriented Yarn)./.............................................................2.3 What developments/modifications have been carried out? (Describe alterations, extensions, etc.)- Phase I: finished in 2011, comprised of 01 Main office, 01 Production workshop divided into 02 subdivision for DTY and ATY including storage area at the rear side of each division.- Phase II: commenced from 2014. The construction of buildings has been completed. The new construction project comprised with two warehouses and one additional workshop for ATY production. The installation of machinery within the new workshop has been completed by approx..70 percent at the time of visit. 2.4 How many employees are employed? Number: ~80 Average per shift: 2.5 Operating periods? Shifts: 02 Days per week: 07 1 Ref: Italon Vietnam | 28 JuL 20153. Construction:3.1 Type of construction? Fire resistant? Yes No PartlyNon combustible? Yes NoBuilding ConstructionClass GF. Area Storey Year RemarkOffice Class A1 2250m 2/S 2011 Production Workshop 1 Class B 26,700m 1/S 2011 Non-sprinkleredWarehouse 1 Class B 23,350 m 1/S 2015 SprinkleredWarehouse 2 Class B 23,350 m 1/S 2015 Production Workshop 2 Class B 23,350 m 1/S 2015 Total land area including building ~69,000 m2 Overall construction class (proportionated by footprint area)Class A1: 3% Class A2: Class B: 97% Class C: Class D: * A1- RC structure, wall& roof; A2- Fire resistive steel structure, RC wall, RC roof; B- RC structure, Render brick or Iron sheet wall, Iron sheet roof; C- Fire non-resistive steel structure, Iron sheet wall& roof; D- Combustible structure, wall& roof.3.2 Are the buildings separated spatially or divided by firewalls and doors? Yes NoInner horizontal cut-offs: Good Fair PoorInner vertical cut-offs: Good Fair Poor
3.3 Can the risk subdivided into several fire areas? Yes No
Number: 01
3.4 Describe proximity's:
North: Public road
West: Vacant land
South: Public road
East: Vacant land
3.5 Are there lightning protection systems? Yes No
Direct lightning: ESE Class
Lightning surge: None
2
4. Process & Occupancies
4.1 What main processes are used?
DTY Process
POY 1st Shafting Heating Cooling False Twisting 2nd Shafting DTY
ATY Process
POY 1st Shafting
POY (Core) 1st Shafting Watering Air jet 2nd Shafting Heat Setting ATY
4.2 What are the maximum temperatures and pressures applied?
Max Pressure: 6.5kg/cm2 Section: Air comp
Max Temp : ~1800C Section: POY heating
4.3 What intermediate and final products are obtained?
- Semi products: there is almost no idle semi product during the process; .......................................
- Final products: ATY (Air Textured Yarn), DTY (Drawn Textured Yarn)./. ....................................
4.4 Are there specific hazardous processes used? Yes No
Wood Working Dry process Spray painting Water reactive substance Dust
Other: None
4.5 Are flammable liquids/gases used in production? Yes No
4.6
Chemical storage:
Kept in a fire-partitioned area: Yes
No
Partially
Mean of storage: Drums Above ground tanks
Jerry can
IBCs
Available anti-spillage dike: Yes No
4.7 Are there explosive dusts? Yes No Type:
4.8 Electronic Data Processing Equipment Yes No
Is there separation by fire walls from adjacent areas? Yes No
Is the location secured from external fire, explosion, water damage? Yes No
4.9 Type of solid material storage?
Bulk Palletized Solid pilling Rack High rack
4.10 Storage conditions? Height: 3m; Aisle width: 1m Min clearance below sprinklers: 0.2m
Stack stability? Good Fair Poor
3
Ventilation fan available? Yes No
4.11 Loading of materials stored? High Medium Low
Combustibility of materials stored? High Medium Low
- It makes a little difference between materials and finished products of the Plant which are classified as non-cellulosic fiber - or manufactured thermoplastic in more detail. In terms of combustibility, thermoplastic fiber is harder to ignite than cotton (cellulosic) fiber. When contacting with heat, thermoplastic fiber will melts, ablates, and burn. The required temperature to ignite thermoplastic material (nylon, polyester) varies between 450-570 Celsius degree, versus 255-400 Celsius degree as the case of cotton fibers. Finished products (ATY, DTY) are drawn and textured fiber which means they have been stiffen through drawing process, causing them to lose their ability to evade flames and ablate. Auxiliary materials: carton packaging boxes, wooden pallets are major additional contribution to the fire load within warehouse area./................................................................................
4.12 Maximum size of storage areas?
- The storage of material and product has almost reached warehouse system’s capacity./. ..................
5. Utilities/ Common Hazards:
5.1 Power Supply source? Public grid Own power station Emergency generator
- Public electrical power 22KV, single power feeders; ......................................................................
- Transformer: 01x3,500kVA + 01x2,500kVA; ...................................................................................
- Generator set: 02 units/ single station, capacity unverified. /. .........................................................
5.2 Transformer protection:
Fixed firefighting systems? Yes No
Type: Automatic fire extinguisher
Fire wall separated? Yes No
5.3 Are there fire-stops for cable penetration through wall openings? Yes No
5.4 Are there steam production facilities? Yes No
What fuels are used for firing boiler, furnaces, heater, etc.? LPG Oil Coal
Other:
Boiling material? Water Other:
4
Number: Max pressure: Purpose:
Inspection validation period Maintenance Frequency
5.5 Are there air compressors? Yes No
Number: 06 Working pressure: 6.5bar Purpose: Production use
5.6
From which source is water supplied?
Public main Well Rivers Lake
Reservoirs
5.7
Internal transport by? Trucks Fork lift trucks Conveyor belts
Others
6. Fire/ Explosion Protection:
6.1 Fire Alarms
Are there manual alarm systems such as push buttons throughout the plant? Yes No
Are manual alarm systems connected to the nearest fire station? Yes No
What types of automatic detection systems are present?
Heat Smoke Flame Gas Rate rise
Which areas are covered by detectors?
- Entire areas./. ............................................................................................................................................
Is there a central alarm stat ion? Yes No Functional: Yes No
Locates at:
Fire station
Gatehouse
Control room(s)
6.2 Fire Water Supplies:
Is the risk connected to the public water supply? Yes No
Own water supply? Yes No
Undergound Tank Aboveground Tank Reservoir Ponds Well Elevated tank
Other Capacity? 01x200m3+01x300 m3
Are there fire pumps which draw from the
đang được dịch, vui lòng đợi..