Page 16 of 80 Report No. 3302407.50IEC 60947-2Clause Requirement + Tes dịch - Page 16 of 80 Report No. 3302407.50IEC 60947-2Clause Requirement + Tes Việt làm thế nào để nói

Page 16 of 80 Report No. 3302407.50

Page 16 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
7.1.7.3 Supplementary requirements for equipment provided with means for padlocking
the open position:
the locking means shall be designed in such a way
that it cannot be removed with the appropriate
padlock(s) installed
N/A
Alternatively, the design may provide padlockable
means to prevent access to the actuator
N/A
test force F applied to the actuator in an attempt to
operate to the closed position (N) :
N/A
rated impulse withstand voltage (kV) : N/A
test Uimp on open main contacts at the test force N/A
7.1.8 Terminals
7.1.8.1 All parts of terminals which maintain contact and
carry current shall be of metal having adequate
mechanical strength
P
Terminal connections shall be such that necessary
contact pressure is maintained
P
Terminals shall be so constructed that the
conductor is clamped between suitable surfaces
without damage to the conductor and terminal
P
Terminal shall not allow the conductor to be
displaced or to be displaced themselves in a
manner detrimental to the operator of equipment
and the insulation voltage shall not be reduced
below the rated value
P
7.1.8.2 Connection capacity
type of conductors : Prepared conductors (with
lug)
P
minimum cross-sectional area of conductor (mm²) : 1 mm2 P
maximum cross-sectional area of conductor
(mm²) :
120 mm2 P
number of conductors simultaneously connectable
to the terminal :
1 P
7.1.8.3 Connection
terminals for connection to external conductors
shall be readily accessible during installation
P
clamping screws and nuts shall not serve to fix any
other component
P
Page 17 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
7.1.8.4 Terminal identification and marking
terminal intended exclusively for the neutral
conductor
P
protective earth terminal N/A
other terminals N/A
7.1.9 part 1 Additional requirements for equipment provided with a neutral pole
When equipment is provided with a pole intended
only for connecting the neutral, this pole shall be
clearly identified to that effect by the letter N (see
7.1.7.4.).
P
A switched neutral pole shall break not before and
shall make not after the other poles
P
For equipment having a value of conventional
thermal current (free air or enclosed, see 4.3.2.1
and 4.3.2.2) not exceeding 63 A, this value shall be
identical for all poles
Same as In P
For higher conventional thermal current values, the
neutral pole may have a value of conventional
thermal current different from that of the other
poles, but not less than half that value or 63 A,
whichever is the higher
Same as In P
if a pole with an appropriate making and breaking
capacity is used as a neutral pole, then all poles,
incl. the neutral pole, shall operate substantially
together.
P
7.1.10 Provisions for protective earthing
7.1.10.1 The exposed conductive parts (e.g. chassis,
framework and fixed parts of metal enclosures)
other than those which cannot constitute a danger
shall be electrically interconnected and connected
to a protective earth terminal for connection to an
earth electrode or to an external protective
conductor
N/A
part 1 This requirement can be met by the normal
structural parts providing adequate electrical
continuity and applies whether the equipment is
used on its own or incorporated in an assembly
N/A
Exposed conductive parts are considered not to
constitute a danger if they cannot be touched on
large areas or grasped with the hand or if they are
of small size (approximately 50 mm x 50 mm) or
are so located as to exclude any contact with live
parts
N/A
Page 18 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
7.1.10.2
part 1
Protective earth terminal
The protective earth terminal shall be readily
accessible and so placed that the connection of the
equipment to the earth electrode or to the
protective conductor is maintained when the cover
or any other removable part is removed
N/A
The protective earth terminal shall be suitably
protected against corrosion
N/A
In the case of equipment with conductive
structures, enclosures, etc., means shall be
provided, if necessary, to ensure electrical
continuity between the exposed conductive parts
the equipment and the metal sheathing of
connecting conductors
N/A
The protective earth terminal shall have no other
function, except when it is intended to be
connected to a PEN conductor (see 2.1.1.5 –
Note). In this case, it shall also have the function of
a neutral terminal in addition to meeting the
requirements applicable to the protective earth
terminal
N/A
7.1.10.3 Protective earth terminal marking and identification
The protective earth terminal shall be clearly and
permanently identified by its marking
N/A
The identification shall be achieved by colour
(green-yellow mark) or by the notation PE, or PEN,
as applicable, in accordance with IEC 60445,
subclause 5.3, or, in the case of PEN, by a
graphical symbol for use on equipment
N/A
Graphical symbol to be used:
60417-2-IEC-5019 Protective earth (ground)
in accordance with IEC 60417-2
N/A
7.1.11 Enclosure for equipment
7.1.11.1 Design
The enclosure, when it is opened: all parts
requiring access for installation and maintenance
are readily accessible
N/A
Sufficient space shall be provided inside the
enclosure
N/A
Page 19 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
The fixed parts of a metal enclosure shall be
electrically connected to the other exposed
conductive parts of the equipment and connected
to a terminal which enables them to be earthed or
connected to a protective conductor
N/A
Under no circumstances shall a removable metal
part of the enclosure be insulated from the part
carrying the earth terminal when the removable
part is in place
N/A
The removable parts of the enclosure shall be
firmly secured to the fixed parts by a device such
that they cannot be accidentally loosened or
detached owing to the effects of operation of the
equipment or vibrations
N/A
When an enclosure is so designed as to allow the
covers to be opened without the use of tools,
means shall be provided to prevent loss of the
fastening devices
N/A
If the enclosure is used for mounting push-buttons,
it shall not be possible to remove the buttons from
the outside of the enclosure
N/A
7.1.11.2 Insulation
If, in order to prevent accidental contact between a
metallic enclosure and live parts, the enclosure is
partly or completely lined with insulating material,
then this lining shall be securely fixed to the
enclosure
N/A
7.1.12 Degree of protection of enclosed equipment
Degree of protection. IP40 for front cover
Test for first characteristic.
Test for first numeral .......................................... : 4 P
Test for second characteristic
Test for second numeral .................................... : N/A
7.1.13
part 1
Conduit pull-out, torque and bending with metallic conduits
Polymeric enclosures of equipment, whether
integral or not, provided with threaded conduit
entries, intended for the connection of extra heavy
duty, rigid threaded metal conduits complying with
IEC 60981, shall withstand the stresses occurring
during its installation such as pull-out, torque,
bending
N/A
Page 20 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
7.2 Performance requirements
7.2.1 Operating condition
7.2.1.1 Closing
For a circuit-breaker to be closed safely on to the
making current corresponding to its rated shortcircuit
making capacity, it is essential that it should
be operated with the same speed and the same
firmness as during the type test for proving the
short-circuit making capacity
P
7.2.1.1.1 Dependent manual closing
For a circuit-breaker having a dependent manual
closing mechanism, it is not possible to assign a
short-circuit making capacity rating irrespective of
the conditions of mechanical operation
N/A
Such a circuit-breaker should not be used in
circuits having a prospective peak making current
exceeding 10 kA
N/A
However, this does not apply in the case of a
circuit-breaker having a dependent manual closing
mechanism and incorporating an integral fastacting
opening release which causes the circuitbreaker
to break safely, irrespective of the speed
and firmness with which it is closed on to
prospective peak currents exceeding 10 kA; in this
case, a rated short-circuit making capacity can be
assigned
N/A
7.2.1.1.2 Independent manual closing
A circuit-breaker having an independent manual
closing mechanism can be assigned a short-circuit
making capacity rating irrespective of the
conditions of mechanical operation
P
7.2.1.1.3 Dependent power closing
At 110% of the rated control supply voltage, the
closing operation performed on no-load shall not
cause any damage to the circuit-breaker.
N/A
At 85% of the rated control supply voltage, the
closing operation shall be performed when the
current established by the circuit-breaker is equal
to its rated making capacity within the limits
allowed by the operation of its relays or releases
and, if a maximum time is stated for the closing
operation, in a time not exceeding this maximum
time limit.
N/A
0/5000
Từ: -
Sang: -
Kết quả (Việt) 1: [Sao chép]
Sao chép!
Page 16 of 80 Report No. 3302407.50IEC 60947-2Clause Requirement + Test Result - Remark VerdictTRF No. IEC60947_2F7.1.7.3 Supplementary requirements for equipment provided with means for padlockingthe open position:the locking means shall be designed in such a waythat it cannot be removed with the appropriatepadlock(s) installedN/AAlternatively, the design may provide padlockablemeans to prevent access to the actuatorN/Atest force F applied to the actuator in an attempt tooperate to the closed position (N) :N/Arated impulse withstand voltage (kV) : N/Atest Uimp on open main contacts at the test force N/A7.1.8 Terminals7.1.8.1 All parts of terminals which maintain contact andcarry current shall be of metal having adequatemechanical strengthPTerminal connections shall be such that necessarycontact pressure is maintainedPTerminals shall be so constructed that theconductor is clamped between suitable surfaceswithout damage to the conductor and terminalPTerminal shall not allow the conductor to bedisplaced or to be displaced themselves in amanner detrimental to the operator of equipmentand the insulation voltage shall not be reducedbelow the rated valueP7.1.8.2 Connection capacitytype of conductors : Prepared conductors (withlug)Pminimum cross-sectional area of conductor (mm²) : 1 mm2 Pmaximum cross-sectional area of conductor(mm²) :120 mm2 Pnumber of conductors simultaneously connectableto the terminal :1 P7.1.8.3 Connectionterminals for connection to external conductorsshall be readily accessible during installationPclamping screws and nuts shall not serve to fix anyother componentPPage 17 of 80 Report No. 3302407.50IEC 60947-2Clause Requirement + Test Result - Remark VerdictTRF No. IEC60947_2F7.1.8.4 Terminal identification and markingterminal intended exclusively for the neutralconductorPprotective earth terminal N/Aother terminals N/A7.1.9 part 1 Additional requirements for equipment provided with a neutral poleWhen equipment is provided with a pole intendedonly for connecting the neutral, this pole shall beclearly identified to that effect by the letter N (see7.1.7.4.).PA switched neutral pole shall break not before andshall make not after the other polesPFor equipment having a value of conventionalthermal current (free air or enclosed, see 4.3.2.1and 4.3.2.2) not exceeding 63 A, this value shall beidentical for all polesSame as In PFor higher conventional thermal current values, theneutral pole may have a value of conventionalthermal current different from that of the otherpoles, but not less than half that value or 63 A,whichever is the higherSame as In Pif a pole with an appropriate making and breakingcapacity is used as a neutral pole, then all poles,incl. the neutral pole, shall operate substantiallytogether.P7.1.10 Provisions for protective earthing7.1.10.1 The exposed conductive parts (e.g. chassis,framework and fixed parts of metal enclosures)other than those which cannot constitute a dangershall be electrically interconnected and connectedto a protective earth terminal for connection to anearth electrode or to an external protectiveconductorN/Apart 1 This requirement can be met by the normalstructural parts providing adequate electricalcontinuity and applies whether the equipment isused on its own or incorporated in an assemblyN/AExposed conductive parts are considered not toconstitute a danger if they cannot be touched onlarge areas or grasped with the hand or if they areof small size (approximately 50 mm x 50 mm) orare so located as to exclude any contact with livepartsN/APage 18 of 80 Report No. 3302407.50IEC 60947-2Clause Requirement + Test Result - Remark VerdictTRF No. IEC60947_2F7.1.10.2part 1Protective earth terminalThe protective earth terminal shall be readilyaccessible and so placed that the connection of theequipment to the earth electrode or to theprotective conductor is maintained when the coveror any other removable part is removedN/AThe protective earth terminal shall be suitablyprotected against corrosionN/AIn the case of equipment with conductivestructures, enclosures, etc., means shall beprovided, if necessary, to ensure electricalcontinuity between the exposed conductive partsthe equipment and the metal sheathing ofconnecting conductors
N/A
The protective earth terminal shall have no other
function, except when it is intended to be
connected to a PEN conductor (see 2.1.1.5 –
Note). In this case, it shall also have the function of
a neutral terminal in addition to meeting the
requirements applicable to the protective earth
terminal
N/A
7.1.10.3 Protective earth terminal marking and identification
The protective earth terminal shall be clearly and
permanently identified by its marking
N/A
The identification shall be achieved by colour
(green-yellow mark) or by the notation PE, or PEN,
as applicable, in accordance with IEC 60445,
subclause 5.3, or, in the case of PEN, by a
graphical symbol for use on equipment
N/A
Graphical symbol to be used:
60417-2-IEC-5019 Protective earth (ground)
in accordance with IEC 60417-2
N/A
7.1.11 Enclosure for equipment
7.1.11.1 Design
The enclosure, when it is opened: all parts
requiring access for installation and maintenance
are readily accessible
N/A
Sufficient space shall be provided inside the
enclosure
N/A
Page 19 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
The fixed parts of a metal enclosure shall be
electrically connected to the other exposed
conductive parts of the equipment and connected
to a terminal which enables them to be earthed or
connected to a protective conductor
N/A
Under no circumstances shall a removable metal
part of the enclosure be insulated from the part
carrying the earth terminal when the removable
part is in place
N/A
The removable parts of the enclosure shall be
firmly secured to the fixed parts by a device such
that they cannot be accidentally loosened or
detached owing to the effects of operation of the
equipment or vibrations
N/A
When an enclosure is so designed as to allow the
covers to be opened without the use of tools,
means shall be provided to prevent loss of the
fastening devices
N/A
If the enclosure is used for mounting push-buttons,
it shall not be possible to remove the buttons from
the outside of the enclosure
N/A
7.1.11.2 Insulation
If, in order to prevent accidental contact between a
metallic enclosure and live parts, the enclosure is
partly or completely lined with insulating material,
then this lining shall be securely fixed to the
enclosure
N/A
7.1.12 Degree of protection of enclosed equipment
Degree of protection. IP40 for front cover
Test for first characteristic.
Test for first numeral .......................................... : 4 P
Test for second characteristic
Test for second numeral .................................... : N/A
7.1.13
part 1
Conduit pull-out, torque and bending with metallic conduits
Polymeric enclosures of equipment, whether
integral or not, provided with threaded conduit
entries, intended for the connection of extra heavy
duty, rigid threaded metal conduits complying with
IEC 60981, shall withstand the stresses occurring
during its installation such as pull-out, torque,
bending
N/A
Page 20 of 80 Report No. 3302407.50
IEC 60947-2
Clause Requirement + Test Result - Remark Verdict
TRF No. IEC60947_2F
7.2 Performance requirements
7.2.1 Operating condition
7.2.1.1 Closing
For a circuit-breaker to be closed safely on to the
making current corresponding to its rated shortcircuit
making capacity, it is essential that it should
be operated with the same speed and the same
firmness as during the type test for proving the
short-circuit making capacity
P
7.2.1.1.1 Dependent manual closing
For a circuit-breaker having a dependent manual
closing mechanism, it is not possible to assign a
short-circuit making capacity rating irrespective of
the conditions of mechanical operation
N/A
Such a circuit-breaker should not be used in
circuits having a prospective peak making current
exceeding 10 kA
N/A
However, this does not apply in the case of a
circuit-breaker having a dependent manual closing
mechanism and incorporating an integral fastacting
opening release which causes the circuitbreaker
to break safely, irrespective of the speed
and firmness with which it is closed on to
prospective peak currents exceeding 10 kA; in this
case, a rated short-circuit making capacity can be
assigned
N/A
7.2.1.1.2 Independent manual closing
A circuit-breaker having an independent manual
closing mechanism can be assigned a short-circuit
making capacity rating irrespective of the
conditions of mechanical operation
P
7.2.1.1.3 Dependent power closing
At 110% of the rated control supply voltage, the
closing operation performed on no-load shall not
cause any damage to the circuit-breaker.
N/A
At 85% of the rated control supply voltage, the
closing operation shall be performed when the
current established by the circuit-breaker is equal
to its rated making capacity within the limits
allowed by the operation of its relays or releases
and, if a maximum time is stated for the closing
operation, in a time not exceeding this maximum
time limit.
N/A
đang được dịch, vui lòng đợi..
Kết quả (Việt) 2:[Sao chép]
Sao chép!
Trang 16 của 80 Báo cáo số 3.302.407,50
IEC 60947-2
khoản Yêu cầu + Kết quả kiểm tra - Ghi chú Verdict
TRF số IEC60947_2F
7.1.7.3 yêu cầu bổ sung cho các thiết bị cung cấp phương tiện cho padlocking
vị trí mở:
các phương tiện khóa được thiết kế theo cách như vậy
rằng nó không thể được loại bỏ bằng thích hợp
ổ khóa (s) cài đặt
N / A
Ngoài ra, thiết kế có thể cung cấp padlockable
có nghĩa là để ngăn chặn truy cập vào các thiết bị truyền động
N / A
lực lượng kiểm tra F áp dụng cho các thiết bị truyền động trong một nỗ lực để
hoạt động đến vị trí đóng ( N):
N / A
xung đánh giá chịu được điện áp (kV): N / A
kiểm tra Uimp trên mở địa chỉ liên lạc chính tại các lực lượng kiểm tra N / A
7.1.8 Thiết bị đầu cuối
7.1.8.1 Tất cả các bộ phận của thiết bị đầu cuối mà duy trì liên lạc và
thực hiện được của kim loại có đầy đủ
sức mạnh cơ khí
P
kết nối thiết bị đầu cuối sẽ được như vậy mà cần thiết
áp lực tiếp xúc được duy trì
P
Thiết bị đầu cuối phải được xây dựng sao cho các
dây dẫn được kẹp giữa các bề mặt phù hợp
mà không có thiệt hại cho các dây dẫn và thiết bị đầu cuối
P
ga sẽ không cho phép các dây dẫn được
di dời hoặc được di dời chính mình trong một
cách gây bất lợi cho các nhà điều hành của các thiết bị
và điện áp cách điện thì không được giảm
dưới giá trị đánh giá
P
7.1.8.2 kết nối công suất
loại dây dẫn: dây dẫn được chế biến (với
tai)
P
khu vực mặt cắt ngang tối thiểu của dây dẫn (mm² ): 1 mm2 P
khu vực cắt ngang lớn nhất của dây dẫn
(mm²):
120 mm2 P
số dây dẫn đồng thời thể kết nối
đến thiết bị đầu cuối:
1 P
7.1.8.3 kết nối
thiết bị đầu cuối để kết nối với dây dẫn bên ngoài
sẽ dễ dàng tiếp cận trong khi cài đặt
P
vít kẹp và hạt sẽ không phục vụ để sửa chữa bất kỳ
thành phần khác
P
Page 17 80 Báo cáo số 3.302.407,50
IEC 60947-2
khoản Yêu cầu + Kết quả kiểm tra - Ghi chú Verdict
TRF số IEC60947_2F
7.1.8.4 ga xác định và ký hiệu đánh dấu
thiết bị đầu cuối dành riêng cho các trung lập
dẫn
P
bảo vệ thiết bị đầu cuối đất N / A
thiết bị đầu cuối khác N / A
7.1.9 phần 1 yêu cầu bổ sung cho thiết bị được cung cấp với một cực trung tính
Khi thiết bị được cung cấp với một cực nhằm mục đích
chỉ để kết nối trung tính, cực này sẽ được
xác định rõ ràng về việc đó bởi thư N (xem
7.1.7.4.).
P
A chuyển cực trung tính sẽ phá vỡ không trước và
sẽ làm cho không sau khi các cực khác
P
Đối với thiết bị có giá trị thông thường của
nhiệt hiện nay (không miễn phí hoặc đính kèm, xem 4.3.2.1
và 4.3.2.2 ) không quá 63 A, giá trị này sẽ
giống hệt nhau cho tất cả các cột
Tương tự như trong P
Đối với giá trị hiện tại nhiệt thường cao hơn,
cực trung tính có thể có một giá trị của truyền
nhiệt hiện tại khác với của người khác
cực, nhưng không ít hơn một nửa giá trị hoặc 63 A,
nào là cao hơn
Tương tự như trong P
nếu một cực với một định thích hợp và phá vỡ
khả năng được sử dụng như một cực trung tính, sau đó tất cả các cột,
bao gồm. cực trung tính, sẽ hoạt động đáng kể
với nhau.
P
7.1.10 Quy định cho nối đất bảo vệ
7.1.10.1 Các bộ phận dẫn điện tiếp xúc (ví dụ như khung xe,
khung và các bộ phận cố định của thùng kim loại)
so với những người khác mà không thể tạo thành một mối nguy hiểm
được điện kết nối với nhau và kết nối
đến một thiết bị đầu cuối đất bảo vệ cho kết nối với một
điện cực trái đất hoặc một bảo vệ bên ngoài
dây dẫn
N / A
phần 1 yêu cầu này có thể được đáp ứng bởi các bình thường
bộ phận kết cấu cung cấp đầy đủ điện
liên tục và áp dụng cho dù thiết bị được
sử dụng riêng hoặc kết hợp trong một lắp ráp
N / A
phần dẫn xúc được xem là không
tạo thành một mối nguy hiểm nếu họ không thể được xúc động trên
khu vực rộng lớn hoặc nắm bắt bằng tay hoặc nếu họ có
kích thước nhỏ (khoảng 50 mm x 50 mm) hoặc
được để nằm như để loại trừ bất kỳ liên hệ với trực tiếp
các bộ phận
N / A
Page 18 80 Báo cáo số 3.302.407,50
IEC 60947-2
khoản Yêu cầu + Kết quả kiểm tra - Ghi chú Verdict
TRF số IEC60947_2F
7.1.10.2
phần 1
thiết bị đầu cuối bảo vệ trái đất
Các thiết bị đầu cuối bảo vệ trái đất sẽ dễ dàng
truy cập và do đó đặt rằng kết nối của
thiết bị điện cực trái đất hoặc các
dây dẫn bảo vệ được duy trì khi nắp
hoặc bất kỳ phần di động khác được lấy ra
N / A
Các thiết bị đầu cuối bảo vệ trái đất được phù hợp
bảo vệ chống ăn mòn
N / A
Trong trường hợp thiết bị với dẫn
cấu trúc, thùng, vv, phương tiện được
cung cấp, nếu cần thiết, để đảm bảo điện
liên tục giữa tiếp xúc với các bộ phận dẫn điện
các thiết bị và các vỏ bọc kim loại của
kết nối dây dẫn
N / A
Các thiết bị đầu cuối bảo vệ trái đất sẽ không có khác
chức năng, trừ khi nó là dự định sẽ được
kết nối với một dây dẫn PEN (xem 2.1.1.5 -
Lưu ý). Trong trường hợp này, nó cũng có chức năng của
một thiết bị đầu cuối trung tính ngoài việc đáp ứng các
yêu cầu đối với các bảo vệ trái đất
thiết bị đầu cuối
N / A
terminal 7.1.10.3 đất bảo vệ đánh dấu và xác định
các thiết bị đầu cuối bảo vệ trái đất được rõ ràng và
vĩnh viễn xác định bởi nó đánh dấu
N / A
Việc xác định phải được thực hiện bằng màu sắc
(đánh dấu màu xanh lá cây, màu vàng) hoặc bằng các ký hiệu PE, hoặc PEN,
như được áp dụng, phù hợp với IEC 60.445,
phân lớp 5.3, hoặc, trong trường hợp của PEN, bởi một
biểu tượng đồ họa để sử dụng trên thiết bị
N / A
biểu tượng đồ họa được sử dụng:
bảo vệ trái đất 60.417-2-IEC-5019 (mặt đất)
theo IEC 60.417-2
N / A
7.1.11 Enclosure cho các thiết bị
7.1.11.1 Thiết kế
Việc bao vây, khi nó được mở ra: tất cả các phần
cần truy cập vào để cài đặt và bảo trì
là dễ dàng tiếp cận
N / A
không gian đầy đủ sẽ được cung cấp bên trong
bao vây
N / A
Page 19 80 Báo cáo số 3.302.407,50
IEC 60947-2
khoản Yêu cầu + Kết quả kiểm tra - Ghi chú Verdict
TRF Không . IEC60947_2F
Các bộ phận cố định của một vỏ kim loại sẽ được
kết nối điện với các tiếp xúc khác
phần dẫn điện của các thiết bị và kết nối
với một thiết bị đầu cuối cho phép họ được nối đất hoặc
kết nối với một dây dẫn bảo vệ
N / A
Trong mọi trường hợp thì một kim loại có thể tháo rời
phần của bao vây được cách ly khỏi phần
mang thiết bị đầu cuối mặt đất khi di động
một phần là ở vị trí
N / A
Các bộ phận rời của bao vây được
bảo đảm vững chắc để các bộ phận cố định bởi một thiết bị như vậy
mà họ không thể vô tình nới lỏng hoặc
tách ra do những tác động của hoạt động của
thiết bị hoặc rung động
N / A
Khi một bao vây như vậy là được thiết kế để cho phép các
trang bìa sẽ được mở mà không sử dụng các công cụ,
phương tiện được cung cấp để ngăn chặn sự mất mát của
các thiết bị buộc
N / A
Nếu bao vây là được sử dụng để gắn push-nút,
nó sẽ không thể loại bỏ các nút từ
bên ngoài của bao vây
N / A
7.1.11.2 cách
Nếu, để phòng tránh tai nạn giữa một
bao vây kim loại và các bộ phận trực tiếp, bao vây là
một phần hoặc hoàn toàn lót bằng vật liệu cách điện,
sau đó lót này sẽ được an toàn cố định vào
vỏ
N / A
7.1.12 Mức độ bảo vệ kèm theo thiết bị
Mức độ bảo vệ. IP40 cho bìa trước
thử nghiệm cho đặc trưng đầu tiên.
Kiểm tra cho số đầu tiên ..................................... .....: 4 P
thử nghiệm cho đặc trưng thứ hai
thử nghiệm cho số thứ hai .................................. ..: N / A
7.1.13
phần 1
Conduit kéo ra, mô-men xoắn và uốn với đường ống kim loại
thùng polymer dùng cho thiết bị, cho dù
không thể tách rời hay không, được cung cấp với ống dẫn luồng
mục, dành cho việc kết nối thêm nặng
nhiệm vụ, kim loại ren cứng nhắc ống dẫn tuân thủ
IEC 60.981, phải chịu đựng những căng thẳng xảy ra
trong quá trình cài đặt của nó như kéo ra, mô-men xoắn,
uốn
N / A
Trang 20 của 80 Báo cáo số 3.302.407,50
IEC 60947-2
khoản Yêu cầu + Kết quả kiểm tra - Ghi chú Verdict
TRF số IEC60947_2F
7.2 yêu cầu Hiệu suất
7.2.1 điều kiện hoạt động
7.2.1.1 Đóng
Đối với một mạch-breaker phải đóng cửa một cách an toàn trên đến
làm hiện tại tương ứng với đánh giá shortcircuit của nó
khả năng làm, điều quan trọng là nó phải
được vận hành với tốc độ như nhau và cùng
độ cứng như trong quá trình thử kiểu cho minh
khả năng làm ngắn mạch
P
7.2.1.1.1 phụ thuộc của nhãn hiệu đóng cửa
Đối với một mạch-breaker có một hướng dẫn phụ thuộc vào
cơ chế đóng cửa, nó không phải là có thể chỉ định một
ngắn mạch làm cho giá khả năng phân biệt
các điều kiện cơ khí hoạt động
N / A
một mạch-breaker như vậy không nên được sử dụng trong
mạch có một đỉnh cao tiềm năng làm cho hiện tại
vượt quá 10 kA
N / A
Tuy nhiên, điều này không áp dụng trong trường hợp của một
mạch-breaker có một hướng dẫn đóng cửa phụ thuộc
cơ chế và kết hợp một fastacting tách rời
phát hành mở mà nguyên nhân của circuitbreaker
để phá vỡ một cách an toàn, không phụ thuộc vào tốc độ
và độ cứng mà nó được đóng lại vào
dòng đỉnh cao trong tương lai vượt quá 10 kA; trong này
trường hợp, công suất làm cho đánh giá ngắn mạch có thể được
gán
N / A
7.2.1.1.2 nhãn hiệu độc lập đóng
mạch-breaker có một nhãn hiệu độc lập
cơ chế đóng cửa có thể được chỉ định một ngắn mạch
làm cho giá năng lực không phụ thuộc vào
điều kiện của cơ khí hoạt động
P
7.2.1.1.3 đóng điện phụ thuộc
Tại 110% nguồn cung cấp điều khiển điện áp đánh giá, các
hoạt động đóng cửa thực hiện trên không tải sẽ không
gây ra bất kỳ thiệt hại cho các mạch-breaker.
N / A
Tại 85% kiểm soát đánh giá cung cấp điện áp, các
hoạt động đóng cửa sẽ được thực hiện khi
hiện tại được thành lập bởi các mạch-breaker bằng
năng lực hoạch định đánh giá của mình trong giới hạn
cho phép do hoạt động của rơ le hoặc phát hành của nó
và, nếu một thời gian tối đa được quy định cho đóng cửa
hoạt động, trong một thời gian không quá tối đa này
thời gian giới hạn.
N / A
đang được dịch, vui lòng đợi..
 
Các ngôn ngữ khác
Hỗ trợ công cụ dịch thuật: Albania, Amharic, Anh, Armenia, Azerbaijan, Ba Lan, Ba Tư, Bantu, Basque, Belarus, Bengal, Bosnia, Bulgaria, Bồ Đào Nha, Catalan, Cebuano, Chichewa, Corsi, Creole (Haiti), Croatia, Do Thái, Estonia, Filipino, Frisia, Gael Scotland, Galicia, George, Gujarat, Hausa, Hawaii, Hindi, Hmong, Hungary, Hy Lạp, Hà Lan, Hà Lan (Nam Phi), Hàn, Iceland, Igbo, Ireland, Java, Kannada, Kazakh, Khmer, Kinyarwanda, Klingon, Kurd, Kyrgyz, Latinh, Latvia, Litva, Luxembourg, Lào, Macedonia, Malagasy, Malayalam, Malta, Maori, Marathi, Myanmar, Mã Lai, Mông Cổ, Na Uy, Nepal, Nga, Nhật, Odia (Oriya), Pashto, Pháp, Phát hiện ngôn ngữ, Phần Lan, Punjab, Quốc tế ngữ, Rumani, Samoa, Serbia, Sesotho, Shona, Sindhi, Sinhala, Slovak, Slovenia, Somali, Sunda, Swahili, Séc, Tajik, Tamil, Tatar, Telugu, Thái, Thổ Nhĩ Kỳ, Thụy Điển, Tiếng Indonesia, Tiếng Ý, Trung, Trung (Phồn thể), Turkmen, Tây Ban Nha, Ukraina, Urdu, Uyghur, Uzbek, Việt, Xứ Wales, Yiddish, Yoruba, Zulu, Đan Mạch, Đức, Ả Rập, dịch ngôn ngữ.