8.4 Thermal switches
All SEG pumps have two sets of thermal switches
incorporated in the stator windings.
Thermal switch, circuit 1 (T1-T3), breaks the circuit
at a winding temperature of approx. 150 °C.
Thermal switch, circuit 2 (T1-T2), breaks the circuit
at a winding temperature of approx. 170 °C (threephase pumps) or 160 °C (single-phase pumps).
The maximum operating current of the thermal
switches is 0.5 A at 500 VAC and cos φ 0.6.
The switches must be able to break a coil in the
supply circuit.
In the case of standard pumps, both thermal
switches can (when closing the circuit after cooling)
generate automatic restarting of the pump via the
controller.
Warning
The pump must not run dry.
An additional level switch must be
installed to ensure that the pump is
stopped in case the stop level switch is
not operating.
Stop the pump when the liquid level
reaches the upper edge of the clamp on
the pump.
Float switches used in explosive
environments must be approved for
this application. They must be
connected to the Grundfos LC, LCD 108
LC 107, LC 110 pump controller via the
intrinsically safe LC-Ex4 barrier to
ensure a safe circuit.
Note This thermal switch must be connected
for all pumps.
Warning
After thermal cutout, explosion-proof
pumps must be restarted manually.
The thermal switch (circuit 2) must be
connected for manual restarting of
these pumps.
Warning
The separate motor-protective circuit
breaker/control box must not be
installed in potentially explosive
environments.
0/5000
Từ: -
Sang: -
Kết quả (Anh) 1: [Sao chép]
Sao chép!
8.4 Thermal switchesAll SEG pumps have two sets of thermal switchesincorporated in the stator windings.Thermal switch, circuit 1 (T1-T3), breaks the circuitat a winding temperature of approx. 150 °C.Thermal switch, circuit 2 (T1-T2), breaks the circuitat a winding temperature of approx. 170 °C (threephase pumps) or 160 °C (single-phase pumps).The maximum operating current of the thermalswitches is 0.5 A at 500 VAC and cos φ 0.6.The switches must be able to break a coil in thesupply circuit.In the case of standard pumps, both thermalswitches can (when closing the circuit after cooling)generate automatic restarting of the pump via thecontroller.WarningThe pump must not run dry.An additional level switch must beinstalled to ensure that the pump isstopped in case the stop level switch isnot operating.Stop the pump when the liquid levelreaches the upper edge of the clamp onthe pump.Float switches used in explosiveenvironments must be approved forthis application. They must beconnected to the Grundfos LC, LCD 108LC 107, LC 110 pump controller via theintrinsically safe LC-Ex4 barrier toensure a safe circuit.Note This thermal switch must be connectedfor all pumps.WarningAfter thermal cutout, explosion-proofpumps must be restarted manually.The thermal switch (circuit 2) must beconnected for manual restarting ofthese pumps.WarningThe separate motor-protective circuitbreaker/control box must not beinstalled in potentially explosiveenvironments.
đang được dịch, vui lòng đợi..
Kết quả (Anh) 2:[Sao chép]
Sao chép!
8.4 Thermal switches
All SEG pumps have two sets of thermal switches
in the stator windings Incorporated.
Thermal switch, circuit 1 (T1-T3), breaks the circuit
at a winding temperature of approx. 150 ° C.
Thermal switch, circuit 2 (T1-T2), breaks the circuit
at a winding temperature of approx. 170 ° C (threephase pumps) or 160 ° C (single-phase pumps).
The maximum operating current of the thermal
switches is 0.5 A at 500 VAC and cos φ 0.6.
The switches Phải thể break a coil in the
supply circuit .
In the case of standard pumps, cả thermal
switches can (closing the circuit after cooling khi)
generate automatic restarting of the pump via the
controller.
Warning
The pump phải dry tremor.
An additional level switch Phải
pump installed to Ensure rằng is
stopped printing case the stop level switch is
not operating.
Stop the pump khi liquid level
Reaches the upper edge of the clamp on
the pump.
Float switches used print explosive
environments Phải approved for
this application. Phải
connected to the Grundfos LC, LCD 108
LC 107, LC 110 pump controller via the
intrinsically safe LC-Ex4 barrier to
Ensure a safe circuit.
Note This thermal switch Phải connected
for all pumps.
Warning
After thermal cutout, explosion- proof
pumps Phải khởi chạy manually.
The thermal switch (circuit 2) phải
connected for manual restarting of
những pumps.
Warning
The motor-protective circuit chia
breaker / control box phải not be
installed print Potentially explosive
environments.
đang được dịch, vui lòng đợi..
 
Các ngôn ngữ khác
Hỗ trợ công cụ dịch thuật: Albania, Amharic, Anh, Armenia, Azerbaijan, Ba Lan, Ba Tư, Bantu, Basque, Belarus, Bengal, Bosnia, Bulgaria, Bồ Đào Nha, Catalan, Cebuano, Chichewa, Corsi, Creole (Haiti), Croatia, Do Thái, Estonia, Filipino, Frisia, Gael Scotland, Galicia, George, Gujarat, Hausa, Hawaii, Hindi, Hmong, Hungary, Hy Lạp, Hà Lan, Hà Lan (Nam Phi), Hàn, Iceland, Igbo, Ireland, Java, Kannada, Kazakh, Khmer, Kinyarwanda, Klingon, Kurd, Kyrgyz, Latinh, Latvia, Litva, Luxembourg, Lào, Macedonia, Malagasy, Malayalam, Malta, Maori, Marathi, Myanmar, Mã Lai, Mông Cổ, Na Uy, Nepal, Nga, Nhật, Odia (Oriya), Pashto, Pháp, Phát hiện ngôn ngữ, Phần Lan, Punjab, Quốc tế ngữ, Rumani, Samoa, Serbia, Sesotho, Shona, Sindhi, Sinhala, Slovak, Slovenia, Somali, Sunda, Swahili, Séc, Tajik, Tamil, Tatar, Telugu, Thái, Thổ Nhĩ Kỳ, Thụy Điển, Tiếng Indonesia, Tiếng Ý, Trung, Trung (Phồn thể), Turkmen, Tây Ban Nha, Ukraina, Urdu, Uyghur, Uzbek, Việt, Xứ Wales, Yiddish, Yoruba, Zulu, Đan Mạch, Đức, Ả Rập, dịch ngôn ngữ.