5. PAINTS (MATERIALS )All paints to be used shall be in accordance with "Painting System" of Specification for Painting. Construction Contractor shall submit the painting systems filled in "Painting System" with the manufacture's product names of the paints to be used, to obtain the Employer's approval. The Construction Contractor shall also submit the instructions and safety data sheet of the manufacturer for each product of the paint. The Construction Contractor shall be required to submit all relevant documents submitted to Employer by the responsible equipment supplier to the Owner.Paints shall be specified:a. For Structural Steel, Pipes, Supports, Components -Indoor places:+ First coat: After blasting and surface preparation, use paint INTERZINC 42, 50 DFT. + Second coat: Surface Preparation - Remove dirt, oil, grease, and other contaminants; INTERGARD 475HS, 200 DFT. + Final coat: Surface Preparation - Remove dirt, oil, grease, and other contaminants; INTERTHANE 990, 50 DFT. + Tolerance DFT refer paint Technical Date Sheet. b. For Structural Steel, Pipes, Supports, Components -Outdoor places:+ First coat: After blasting and surface preparation, use paint INTERZINC 42, 50 DFT. + Second coat: Surface Preparation - Remove dirt, oil, grease, and other contaminants; INTERGARD 475HS, 200 DFT. + Final coat: Surface Preparation - Remove dirt, oil, grease, and other contaminants; INTERTHANE 990, 70 DFT. + Tolerance DFT refer paint Technical Date Sheet. c. For Galvanized Steel (i.e. handrails, stanchions, ladders, guards knee-rails,toe plates):+ Touch up: The galvanized layer which is damaged will be touched up by Interzinc 42 (epoxy zinc) by 50 microns before apply the primer coat (Interseal 670HS) + Primer coat: Product after galvanized will be Paint INTERSEAL 670HS ,100 DFT. + Final coat: Surface Preparation - Remove dirt, oil, grease, and other contaminants; INTERTHANE 990 , 50 DFT. + Tolerance DFT refer paint Technical Date Sheet.
đang được dịch, vui lòng đợi..