What to do when not Functioning Pro

What to do when not Functioning Properly
The following cases are not malfunctions.
State of trouble
•The chiller is stopped during winter or nights when the outdoor temperature falls to a round 0°C, and only the pump runs(chiller is receiving electricity).
•When stopped the compressor inside the chiller is hot if touched (Chiller is receiving electricity).
Case
The chiller is equipped with a pump for preventing water inside the piping from freezing that force operates. For details, see the wiring diagram.
Electricity is supplied to the crank case heater to warm the compressor so that the chiller can be started smoothly. This is not a malfunction.
Before requesting after-sales service, please check the following items.
State of trouble
Operation lamp
Cause
Disposal
1.Water
pump/com-pressor doesn’t start at all


2.The water pump starts but water doesn’t circulate.


3.Compressor does not work but the thermostat does

4.Compressor stops while cooling and will not restart
automatically


5.Compressor stops shortly after cooling starts (After 10 minutes, the unit restarts after pressing the operation button)



6.Chilled water temperature is abnormal.
Off
Off
ON
Off
Off
ON
1a.Was there a power failure?
1b.Is the power supply switch turned on?
1c.Is the power supply fuse blown?
2a.Is there a lack of make-up water?
2b.Is the water pump turning in reverse?
2c.Is the valve in the water piping open sufficiently?
3a.Is the chilled water regulating valve opened enough?
Is the setting temp, properly adjusted?

4a.Are the chilled and condenser water flow regulating valve open the proper amount?
4b.Is the setting temp, properly adjusted?
4c.Is the strainer for the condenser water line clogged?
5a. Is condenser water flowing to the condenser? Is water level low?
5b. Is the condenser water pump down?
5c.Is the condenser line strainer cloqged?
5d. (For system with cooling tower)
1) ls the tower fan rotating in reverse? Has it stopped?
2) ls the tower strainer clogged?
3) ls the nozzle is clogged?
6a. Is the chilled water valve closed?
6b. Is the setting temp, properly set on?
1a.To be safe, turn the power supply switch off temporarily.
1b.Turn the power supply switch on.
1c.Replace the power supply fuse.
2a.Replenish sufficiently with make-up water. (Water is not pumped unless the water pump and suction pipe are filled with water.)
2b.Correct the turning direction of the water pump.
2c.Open the valve in the water piping sufficiently.
3a.Open the chilled water regulating valve.
3b.Properly adjust the setting temp.
4a. Open the flow regulating valve the proper amount.
4b. Properly adjust the setting temp.
4c. Unclog the strainer.
5a. Supply a sufficient amount of condenser water.
5b. Activate the condenser water pump.
5c.Unclog the strainer.
5d. (See the cooling tower instruction manual)
1) Set fan rotation in the correct direction.
2) Unclog the strainer.
3) Inspect and clean.
6a. Open the valve.
6b. Adjust the setting temperature..
• If, after checking the items given above, the chiller is still not functioning properly, contact your DAIKIN dealer. Do not attempt to repair the problem yourself. When you call, you should be prepared to give a description of the state If trouble and the model.
0/5000
Từ: -
Sang: -
Kết quả (Việt) 1: [Sao chép]
Sao chép!
What to do when not Functioning ProperlyThe following cases are not malfunctions.State of trouble•The chiller is stopped during winter or nights when the outdoor temperature falls to a round 0°C, and only the pump runs(chiller is receiving electricity).•When stopped the compressor inside the chiller is hot if touched (Chiller is receiving electricity).CaseThe chiller is equipped with a pump for preventing water inside the piping from freezing that force operates. For details, see the wiring diagram.Electricity is supplied to the crank case heater to warm the compressor so that the chiller can be started smoothly. This is not a malfunction.Before requesting after-sales service, please check the following items.State of troubleOperation lampCauseDisposal1.Waterpump/com-pressor doesn’t start at all2.The water pump starts but water doesn’t circulate.3.Compressor does not work but the thermostat does4.Compressor stops while cooling and will not restartautomatically5.Compressor stops shortly after cooling starts (After 10 minutes, the unit restarts after pressing the operation button)6.Chilled water temperature is abnormal.OffOffONOffOffON1a.Was there a power failure?1b.Is the power supply switch turned on?1c.Is the power supply fuse blown?2a.Is there a lack of make-up water?2b.Is the water pump turning in reverse?2c.Is the valve in the water piping open sufficiently?3a.Is the chilled water regulating valve opened enough?Is the setting temp, properly adjusted?4a.Are the chilled and condenser water flow regulating valve open the proper amount?4b.Is the setting temp, properly adjusted?4c.Is the strainer for the condenser water line clogged?5a. Is condenser water flowing to the condenser? Is water level low?5b. Is the condenser water pump down?5c.Is the condenser line strainer cloqged?5d. (For system with cooling tower)1) ls the tower fan rotating in reverse? Has it stopped?2) ls the tower strainer clogged?3) ls the nozzle is clogged?6a. Is the chilled water valve closed?6b. Is the setting temp, properly set on?1a.To be safe, turn the power supply switch off temporarily.1b.Turn the power supply switch on.1c.Replace the power supply fuse.2a.Replenish sufficiently with make-up water. (Water is not pumped unless the water pump and suction pipe are filled with water.)2b.Correct the turning direction of the water pump.2c.Open the valve in the water piping sufficiently.3a.Open the chilled water regulating valve.3b.Properly adjust the setting temp.4a. Open the flow regulating valve the proper amount.4b. Properly adjust the setting temp.4c. Unclog the strainer.5a. Supply a sufficient amount of condenser water.5b. Activate the condenser water pump.5c.Unclog the strainer.5d. (See the cooling tower instruction manual)1) Set fan rotation in the correct direction.2) Unclog the strainer.3) Inspect and clean.6a. Open the valve.6b. Adjust the setting temperature..• If, after checking the items given above, the chiller is still not functioning properly, contact your DAIKIN dealer. Do not attempt to repair the problem yourself. When you call, you should be prepared to give a description of the state If trouble and the model.
đang được dịch, vui lòng đợi..
Kết quả (Việt) 2:[Sao chép]
Sao chép!
Phải làm gì khi không chức năng đúng
Các trường hợp sau đây không trục trặc.
Nhà nước gặp khó khăn
• Các máy làm lạnh được dừng lại trong mùa đông hoặc đêm khi nhiệt độ ngoài trời rơi vào một vòng 0 ° C, và chỉ chạy máy bơm (máy làm lạnh được nhận điện).
• Khi dừng máy nén bên trong máy làm lạnh là nóng nếu đụng (Chiller đang nhận được điện).
Trường hợp
của máy làm lạnh được trang bị với một máy bơm để ngăn ngừa nước bên trong đường ống bị đóng băng lực lượng mà hoạt động. Để biết chi tiết, xem sơ đồ hệ thống dây điện.
Điện được cung cấp cho các trường hợp tay quay nóng để làm ấm máy nén để các máy làm lạnh có thể được bắt đầu suôn sẻ. Đây không phải là một sự cố.
Trước khi yêu cầu sau bán hàng dịch vụ, xin vui lòng kiểm tra các mục sau đây.
Nhà nước gặp khó khăn
Operation đèn
Nguyên nhân
nghiền rác
1.Water
bơm / com-huyết áp không bắt đầu ở tất cả 2.The bơm nước bắt đầu nhưng nước doesn ' t hầm. 3.Compressor không làm việc nhưng nhiệt làm 4.Compressor sẽ dừng lại, làm mát và sẽ không khởi động lại tự động 5.Compressor ngừng ngay sau khi bắt đầu làm mát (Sau 10 phút, khởi động lại máy sau khi nhấn nút hoạt động) nước 6.Chilled nhiệt độ bất thường. Tắt Tắt ON Tắt Tắt ON 1a.Was có mất điện? 1b.Is chuyển đổi nguồn cung cấp điện bật? 1c.Is việc cung cấp điện cầu chì thổi? 2a.Is có một thiếu make-up nước? 2b .là những bước ngoặt bơm nước ngược? 2c.Is van trong hệ thống đường ống nước mở đủ? 3a.Is nước ướp lạnh điều chỉnh van mở đủ? Là temp thiết lập, điều chỉnh đúng? 4a.Are sự điều tiết lưu lượng nước lạnh và ngưng tụ van mở đúng số lượng? 4b.Is temp thiết lập, điều chỉnh đúng? 4c.Is bộ lọc cho dòng nước ngưng bị tắc? 5a. Được nước ngưng tụ chảy vào bình ngưng? Là mực nước thấp? 5b. Là nước ngưng bơm xuống? 5c.Is dòng tụ lọc cloqged? 5d. (Đối với hệ thống với tháp giải nhiệt) 1) ls quạt tháp quay ngược lại? Có nó dừng lại? 2) ls bộ lọc bị tắc tháp? 3) ls vòi phun bị tắc? 6a. Là các van nước lạnh đóng cửa? 6b. Là tạm thời thiết lập, thiết lập đúng trên? 1a.To được an toàn, bật nguồn điện tắt tạm thời. 1b.Turn chuyển đổi nguồn cung cấp điện trên. 1c.Replace việc cung cấp điện cầu chì. 2a.Replenish đủ với make-up nước. (Nước không bơm trừ khi các máy bơm nước và ống hút được chứa đầy nước.) 2b.Correct hướng quay của máy bơm nước. 2c.Open van trong hệ thống đường ống nước đầy đủ. 3a.Open van điều tiết nước lạnh. 3b .Properly điều chỉnh nhiệt độ thiết lập. 4a. Mở luồng điều tiết van đúng số lượng. 4b. Đúng điều chỉnh nhiệt độ thiết lập. 4c. Thông tắc bộ lọc. 5a. Cung cấp đủ lượng nước ngưng tụ. 5b. Kích hoạt máy bơm nước ngưng tụ. 5c.Unclog bộ lọc. 5d. (Xem hướng dẫn nhãn hiệu tháp giải nhiệt) 1) Thiết xoay quạt theo hướng đúng. 2) thông tắc bộ lọc. 3) Kiểm tra và sạch sẽ. 6a. Mở van. 6b. Điều chỉnh nhiệt độ cài đặt .. • Nếu, sau khi kiểm tra các mặt hàng nêu trên, các máy làm lạnh vẫn không hoạt động đúng, liên hệ với đại lý DAIKIN của bạn. Đừng cố gắng để sửa chữa các vấn đề chính mình. Khi bạn gọi, bạn nên chuẩn bị để cung cấp cho một mô tả của nhà nước Nếu gặp khó khăn và các mô hình.































































đang được dịch, vui lòng đợi..
 
Các ngôn ngữ khác
Hỗ trợ công cụ dịch thuật: Albania, Amharic, Anh, Armenia, Azerbaijan, Ba Lan, Ba Tư, Bantu, Basque, Belarus, Bengal, Bosnia, Bulgaria, Bồ Đào Nha, Catalan, Cebuano, Chichewa, Corsi, Creole (Haiti), Croatia, Do Thái, Estonia, Filipino, Frisia, Gael Scotland, Galicia, George, Gujarat, Hausa, Hawaii, Hindi, Hmong, Hungary, Hy Lạp, Hà Lan, Hà Lan (Nam Phi), Hàn, Iceland, Igbo, Ireland, Java, Kannada, Kazakh, Khmer, Kinyarwanda, Klingon, Kurd, Kyrgyz, Latinh, Latvia, Litva, Luxembourg, Lào, Macedonia, Malagasy, Malayalam, Malta, Maori, Marathi, Myanmar, Mã Lai, Mông Cổ, Na Uy, Nepal, Nga, Nhật, Odia (Oriya), Pashto, Pháp, Phát hiện ngôn ngữ, Phần Lan, Punjab, Quốc tế ngữ, Rumani, Samoa, Serbia, Sesotho, Shona, Sindhi, Sinhala, Slovak, Slovenia, Somali, Sunda, Swahili, Séc, Tajik, Tamil, Tatar, Telugu, Thái, Thổ Nhĩ Kỳ, Thụy Điển, Tiếng Indonesia, Tiếng Ý, Trung, Trung (Phồn thể), Turkmen, Tây Ban Nha, Ukraina, Urdu, Uyghur, Uzbek, Việt, Xứ Wales, Yiddish, Yoruba, Zulu, Đan Mạch, Đức, Ả Rập, dịch ngôn ngữ.