Load or through fault currents at the two ends of a protected
feeders are in antiphase (using the normal relay convention for
direction), whilst during an internal fault the (conventional)
currents tend towards the in-phase condition. Hence, if the
phase relationship of through fault currents is taken as a
reference condition, internal faults cause a phase shift of
approximately 180° with respect to the reference condition.