The most important consideration in the application of auto-reclosing to EHV transmission lines is the maintenance of system stability and synchronism. The problems involved are dependent on whether the transmission system is weak or strong. With a weak system, loss of a transmission link may lead quickly to an excessive phase angle across the CB used for re-closure, thus preventing a successful re-closure. In a relatively strong system, the rate of change of phase angle will be slow, so that delayed auto-reclose can be successfully applied.An illustration is the interconnector between two power systems as shown in Figure 14.4. Under healthy time that can be tolerated without loss of system stability. This will normally require transient stability studies to be conducted for a defined set of power system configurations and fault conditions. With knowledge of protection and circuit breaker operating characteristics and fault arc de-ionisation times, the feasibility of high-speed auto-reclosing can then be assessed. These factors are now discussed.